5.1.5
Fuel Submenu
Menu item
Display
Description
I/C
OpMode
One of the
modes:
Operating mode of fuel
system. The mode is displayed
in the main menu if no error
occurred.
I
init
Software module initializes
I
active
Tank is available and will be
used.
I
offline
Fuel module is offline and will
not be monitored by the EM
control software.
I
standby
Tank is available.
I
error
Fuel module is in error status.
I
StateRpl
One of the
replies:
State reply. System answer on a
user command (CMD).
init
Software module initializes
I
run
Fuel module reports “Ready for
operating”.
I
offline
Fuel module reports request to
switch as soon as possible to
“offline” in OpMode.
I
CMD
One of the
commands:
Command to be entered by
user.
no command
No command in queue
I+C
go online
Start Fuel module
C
go offline
Stop Fuel module
C
cancel command Cancel command in queue
C
Level
x.x %
Filling status in %
I
Content
xxx L
Filling status in liters
I
Remain
x.xx d
Available remaining life at
current consumption in days
I
Total cons
xxxx L
Total consumption since last
reset
I
Reset Counters*
Resetting operating counters
C*
Error List
Number in
hexadecimal
format
All active events are displayed
one after another with their
number and a short text and
can be confirmed.
I+C
Legend:
*
Item is only displayed if the access level is service
I/C
Information/Command
Table 5-5 Fuel submenu