Operating
Energy Manager 1.3 - Instruction Manual
39
5.1.4
Battery Submenu (Batt)
Menu item
Display
Description
I/C
OpMode
1 of the following
modes:
Operating mode of the battery.
The mode is displayed in the
main menu if no error
occurred.
init
Software module initializes
I
offline
Battery is offline and will not be
monitored by EM control
software.
I
error
Error detected, battery cannot
run.
I
blk charge
Battery charges with fixed
current
I
flt charge
Genset is running or site is
running on grid. Voltage is at
configured float voltage to
maintain voltage at floating
level (default: 54 V).
I
eboost ch.
Battery charges with fixed
voltage.
I
discharge
Battery is in discharge.
I
eboost ch
Battery is in extended boost
charge and will be charged
for10 h (time is set in LAA).
I
equali ch
Battery is in equalization
charge and will be charged for
20 h (time is set in LAA).
I
v_sub_low
Battery is not charged or
discharged and the voltage is
below the float voltage.
I
StateRpl
One of the
replies:
State reply. System answer to a
user command (CMD).
init
SW initializes.
I
run
Battery module reports “Ready
for operating”.
I
offline
Battery module reports request
to switch to offline operating
mode as soon as possible.
I
CMD
One of the
commands:
Command to be entered by a
user.
no command
No command stands in a
queue.
I+C
go online
Start battery module
C
go offline
Stop battery module
C
cancel cmd
Cancel command in queue.
C
Voltage
x.xx V
Battery voltage
I