![Heliocentris Energy Manager 1.3 Instruction Manual Download Page 24](http://html.mh-extra.com/html/heliocentris/energy-manager-1-3/energy-manager-1-3_instruction-manual_2120651024.webp)
Getting Started
24
Energy Manager 1.3 - Instruction Manual
4.4
How to Ground the Energy Manager
In order to ground the Energy Manager, the ground cable must be
connected at the rear side of the Energy Manager. If a genset is installed,
the other end of the grounding cable is in general connected with the
grounding of the rectifier. It can also be connected with the rack
grounding or another ground.
Ground cable (green-yellow protective conductor, wire cross
section at least 6 mm², included in delivery)
Screw driver
M5x10 screws
Ground the Energy Manager as follows:
1.
Remove screw with hex key.
2.
Tighten the earth circuit connector of the ground cable with the screw
on the rear side of the Energy Manager.
Figure 4-1 Grounding connection (1)
3.
Connect the other end of the ground cable to the appropriate
grounding.
4.5
How to Connect Energy Manager to Power
Supply
The power supply of the Energy Manager is connected to the priority load
of the rectifier, e.g. battery.
2-pin cable
Small screw driver
Connector
NOTICE
Property damage due to incorrect polarity !
Incorrect polarity will permanently damage the device. Watch
out for correct polarity of the connection:.
Connect the power cable as follows: