Operating
44
Energy Manager 1.3 - Instruction Manual
5.1.8
Free Cooling Unit Submenu (FCU)
Menu item
Display
Description
I/C
OpMode
One of the
modes:
Operating mode of the free
cooling unit. The mode is
displayed also in the main
menu if no error occurred.
init
Software module initializes.
I
active
FCU is active.
I
offline
FCU module is offline and will
not be started by the EM
control software.
I
standby
FCU is available
I
error
FCU module is in error status.
I
StateRpl
One of the
replies:
State reply. System answer to a
user command (CMD).
init
Software moduleinitializes.
I
run
FCU module reports “Ready
for operating”.
I
offline
FCU module reports request to
switch as soon as possible to
offline operation mode..
I
test
FCU module indicates that it is
in “Test mode” (i.e., manual
switching on / off is possible).
I
CMD
One of the
commands:
Command to be entered by
user.
no command
No command stands in a
queue.
I+C
go online
Start FCU module.
C
go offline
Stop FCU module.
C
go testmode
Set FCU module to test mode.
C
cancel command Cancel command in queue.
C
Relay
One of the
commands:
Available in test mode.
Relay on
Switch FCU controller reset
relay to manual.
C
Relay off
Switch FCU controller reset
relay off to manual
C
Temp
x.x °C
Room temperature of FCU -
controlled shelter.
I
Fanspeed
xxx RPM
Fan speed of FCU in volts.
I
PWM
x.x %
Percentage of max value only
for FCU if controlled via
analog signal.
I
Op-Time
x.xx h
Operating hours of FCU.
I
Reset Counter*
Reset operating counters.
C*