Getting Started
22
Energy Manager 1.3 - Instruction Manual
4.3.2
Port Assignment
Port assignments can be delivered as configuration package or
administered via LAA. As default configuration no ports are assigned.
The port assignment described in this chapter is 1possibility to configure
the ports and does not necessarily correspond to the realized solution.
The contact allocation may not exceed values given in
Table 4-1
:
Contact
Value
Digital output: REL 1 – 16
Max. switching current: 0.5 A
Max. switching voltage: 60 V DC
Max. switching power: 30 W
Digital input: DI 1 – 12
Low Level: 0 – 2 V DC
High Level: 4 – 35 V DC
Analog output: AO 1 – 2
Output voltage: 0 – 10 V DC, max. 5 mA
DC
Analog inputs: -100 VDC 1 – 4
-100 – 0 VD
Analog inputs: AI1 – AI20
0–20 mA / 0–5, 0–10 , 0–30 VDC
(configurable)
Analog inputs: T1 – 8
PT 1000
RS 485
Not used in standard configuration
GND
GND
+24 VDC
+24 VDC max. 50 W
Table 4-1 Standard contact allocation
Depending on the installed modules Heliocentris recommends a
configuration as indicated in
. The assignments may differ
because of the installed software and hardware components.
Port
Default sensor
Connection
REL1
Genset 1 acc/start
REL2
Genset 1 glow (fixed in firmware)
REL3
Genset 1 crank (fixed in firmware)
REL4
Genset 1 load switch / ATS 1
REL5
ATS 2
REL7
Battery 1 LVD
REL9
Genset 2 acc/start
REL10
Genset 2 glow (fixed in firmware)
REL11
Genset 2 crank (fixed in firmware)
REL12
Aircon management modul 1
REL13
Aircon management modul 2
REL14
Aircon management modul 3
REL15
Aircon management modul 4
REL16
Aircon management modul 5
DI1
Genset run signal
Contact allocation
Configuration example