Operating
54
Energy Manager 1.3 - Instruction Manual
5.4
How to Reset Counters and Statistics Displays
After replacing a hardware component of the system like genset or aircon,
the counter display for this component has to be reset by the service.
TIP
This function is reserved for users with service rights.
Reset counters and statistics data as follows:
1.
In the
main menu
, select
Login.
2.
Enter the appropriate password.
3.
In the
main menu
, select the respective module.
4.
Confirm with
OK
.
5.
Select
Reset Counters.
6.
Confirm with
OK
.
The counter value is reset to 0 and starts counting from 0 again.
5.5
How to Observe Alarms and Other Events
Messages concerning alarms and other events are displayed in LCD of the
control panel. They indicate significant changes in the state of the Energy
Manager and the affected systems or inform about the behavior of the
system.
For each event an event code and a short description are displayed by the
system.
The value range of the event code is per module 0 – FF in hexadecimal
format. The lower the code, the more severe is the event. The following
event levels are distinguished:
Event code
Event level
01 - 9F
Alarm
In case of alarms, the normal operating mode is no
longer available. The respective modules are
switched off or an emergency program is started.
a1 - ff
Warning
Warnings do not affect operation.
<ff
Information
Table 5-18 Event codes and levels
NOTICE
Property damage if alarms are neglected!
In case of alarms (event code 0-7), notify the service of
Heliocentris or an authorized partner.