X48 Analog Input (PLC) at the LE
D-sub terminal
(female) 25-pin
Assignment
1 I
1
+ Constant current for Pt 100
2 I
1
– Constant current for Pt 100
3 U
1
+ Measuring input for Pt 100
4 U
1
– Measuring input for Pt 100
5 I
2
+ Constant current for Pt 100
6 I
2
– Constant current for Pt 100
7 U
2
+ Measuring input for Pt 100
8 U
2
– Measuring input for Pt 100
9
Do not use
10
Do not use
11
Do not use
12
Do not use
13
Do not use
14
Analog input 1 –10 V to +10 V
15
Analog input 1 0 V (reference potential)
16
Analog input 2 –10 V to +10 V
17
Analog input 2 0 V (reference potential)
18
Analog input 3 –10 V to +10 V
19
Analog input 3 0 V (reference potential)
20 to 25
Do not use
Housing External
shield
The correct polarity of analog inputs is essential.
X15, X16, X17, X18 Analog inputs on the PL 410 B
Terminal Assignment
1
–10 V to +10 V
2
0 V (reference potential)
3 Shield
3–38
TNC 370 D
Mounting and Electrical Installation
July 02