8 Troubleshooting – Possible faults
170
F014
Boiler return
temp.
short circuit
•
Short circuit in the sensor or
sensor cable
•
Connect sensor
•
Replace cable
•
Check terminal (check plug
for secure fit)
•
Exchange the faulty sensor
(plug on the I/O circuit board)
with a different sensor
•
If a different fault appears, the
sensor should be replaced
•
If the same fault appears, the
I/O circuit board should be
replaced
F015
Boiler return
temp.
open circuit
•
Sensor is faulty
•
Open circuit in sensor cable
•
Sensor not connected
•
Connect sensor
•
Replace cable
•
Check terminal (check plug
for secure fit)
•
Exchange the faulty sensor
(plug on the I/O circuit board)
with a different sensor
•
If a different fault appears, the
sensor should be replaced
•
If the same fault appears, the
I/O circuit board should be
replaced
F016
Outside tempera-
ture short cir-
cuit
•
Short circuit in the sensor or
sensor cable
•
Connect sensor
•
Replace cable
•
Check terminal (check plug
for secure fit)
•
Exchange the faulty sensor
(plug on the I/O circuit board)
with a different sensor
•
If a different fault appears, the
sensor should be replaced
•
If the same fault appears, the
I/O circuit board should be
replaced
F017
Outside tempera-
ture open cir-
cuit
•
Sensor is faulty
•
Open circuit in sensor cable
•
Sensor not connected
•
Connect sensor
•
Replace cable
•
Check terminal (check plug
for secure fit)
•
Exchange the faulty sensor
(plug on the I/O circuit board)
with a different sensor
•
If a different fault appears, the
sensor should be replaced
•
If the same fault appears, the
I/O circuit board should be
replaced
No.
Fault
Cause
Remedy
Table 8/1 - Faults
Summary of Contents for Compact 25
Page 1: ...hdg bavaria com HDG Compact 25 80 Operation Manual ...
Page 2: ......
Page 186: ...12 Index 186 HDG Compact 25 35 Version 2 de HDG Bavaria GmbH Oktober 2007 ...
Page 187: ......