6 Using the heating system – Structure of the menus
126
4-22
Control
R-2 Flue gas fan
Minimum
( 40)
40%
•
Rpm flue gas fan
For minimum primary air volume.
(0 - 100 %)
4-23
Control
R-2 Flue gas fan
Maximum
( 70)
70%
•
Rpm flue gas fan
For maximum primary air volume.
(0 - 100 %)
4-24
Control
R-3 O2 setpoint for
comb. chamber min
( 8.0)
8.0%
•
Residual oxygen preset value
For minimum combustion chamber temperature.
(0.0 - 21.0 %)
4-25
Control
R-3 O2 setpoint for
comb. chamber max
( 8.0)
8.0%
•
Residual oxygen preset value
For maximum combustion chamber temperature.
(0.0 - 21.0 %)
4-26
Control
PID_3 O2
Amplification (P)
( 10.0)
10.0%
•
Amplification factor for residual oxygen
For “Combustion control” or “Combustion and output
control” mode.
4-27
Control
PID_3 O2
Lag time (I)
( 86.0)
86.0s
•
Lag time for residual oxygen
For “Combustion control” or “Combustion and output
control” mode.
4-28
Control
PID_3 O2
Advance time (D)
( 0.0)
0.0s
•
Advance time for residual oxygen
For “Combustion control” or “Combustion and output
control” mode.
4-30
Control
PID_3 sec. air
O2 Minimum
( 10)
10%
•
Secondary air volume minimum value
Depends on residual oxygen.
(0 - 100 %)
4-31
Control
PID_3 sec. air
O2 Maximum
( 100)
100%
•
Secondary air volume maximum value
Depends on residual oxygen.
(0 - 100 %)
4-32
Control
O2 fuel change
Cycle time (TS)
( 5)
5s
•
Cycle time
When PID_3 has reached its limit value, the fuel quantity
in the set cycle time is increased or decreased in percen-
tage increments. (see
4-33
and
4-34
)
No.
Display
Description
Table 6/6 - System level / 4 - Control