8 Troubleshooting – Possible faults
176
F153
Safety circuit
Klixon feeding
syst.
•
Motor too hot
•
Cable not connected
•
Motor overload
•
Check current consumption
and connection
•
Check connection
F154
Safety circuit
Klixon dosage
•
Motor too hot
•
Cable not connected
•
Motor overload
•
Check current consumption
and connection
•
Check connection
F155
Safety circuit
Klixon delivery
syst
•
Motor too hot
•
Cable not connected
•
Motor overload
•
Check current consumption
and connection
•
Check connection
F160
Error external
feeding units
•
Terminals 32 + 33 not
bridged
•
External conveyor fault
•
Check terminals
F161
Klixon
Ash auger
•
Motor too hot
•
Cable not connected
•
Motor overload
•
Check current consumption
and connection
F162
Klixon
boiler cleaning
•
Motor too hot
•
Cable not connected
•
Motor overload
•
Check current consumption
and connection
F170
No connection to
GSM module
•
No telephone card in GSM
module
•
No GSM module available
•
Check GSM module
•
Cable not connected
•
Parameter
1-10
incorrectly
set
F171
GSM error, no
signal
No network or
SIM card
•
Radio network not available
•
Antenna connection
•
No SIM card in the modem
•
Insert SIM card
•
Connect antenna cable
F172
Modem not con-
nected
•
Cable at interface of PC (RS
232) or telephone box not
connected
•
Check cables
•
Fault is only activated during
remote maintenance with
modem
F180
Transport module
(IO21) wrong
version
•
Wrong transport module
•
Exchange transport module
•
Notify HDG customer service
F181
Phase L2+L3 con-
nected
•
Wrong phase setting
•
Notify HDG customer service
F200
CAN data trans-
fer wrong ID
•
System malfunction
•
Notify HDG customer service
F201
CAN-BUS
error(read)
•
System malfunction
•
Notify HDG customer service
No.
Fault
Cause
Remedy
Table 8/1 - Faults