3 Mode of operation – Functional description
24
Example:
Outside temperature
-5 °C
Steepness
1.6
Parallel shift
5 °C
With these presumed values, you can see in “Figure 3/8 - Diagram of
the temperature of water leaving the boiler” that the heating circuit
supply temperature of the water is
67 °C
.
If an indoor thermostat unit is also connected, the comparison bet-
ween the preset and the actual room temperature and the room in-
fluence factor are also included in the calculation of the required
water temperature leaving the boiler. The temperature difference is
multiplied by the room influence factor and is then added to the
preset room temperature. The room influence factor expresses how
strongly any deviation of the room temperature should affect the
water temperature leaving the boiler.
If no indoor thermostat unit is connected, the preset day and night
temperatures are used for the calculation.
O
UTSIDE
TEMPERATURE
SWITCH
-
OFF
If the outside temperature exceeds the preset room temperature or
the preset outside switch-off temperature, the status of the heating
circuit changes to
OFF
.
I
NDOOR
THERMOSTAT
UNIT
If an indoor thermostat unit is connected, the current target room
temperature is calculated from the preset day and night room tem-
peratures, the room influence factor and the current measured room
temperature.
H
EATING
SYSTEMS
FOR
THE
HEATING
CIRCUITS
In the group of parameters for the "hydraulic system", the correspon-
ding heating system is configured for each of the various heating cir-
cuits.
Figure 3/8 - Diagram of the temperature of water leaving the boiler
3.5
3.0
2.5
2.0
1.0
1.5
0.5
20
15
10
5
0
-5
-10
-15
-20
20
30
4
0
50
60
7
0
8
0
1.6
0.8
Pa
ral
lel
sh
ift
External temperature
Supp
ly temperature
Summary of Contents for Compact 25
Page 1: ...hdg bavaria com HDG Compact 25 80 Operation Manual ...
Page 2: ......
Page 186: ...12 Index 186 HDG Compact 25 35 Version 2 de HDG Bavaria GmbH Oktober 2007 ...
Page 187: ......