8 Troubleshooting – Possible faults
168
F002
Grate blocked
down
•
Grate is jammed
•
Limit switch is not correctly
set
•
Limit switch is incorrectly
connected
•
Grate motor is faulty
•
Check grate mechanics
•
Readjust limit switch
•
Have limit switch connection
checked by a qualified electri-
cian
•
Have the grate motor repla-
ced by a heating technician
F003
Delivery system
fill time excee-
ded
•
No material available
•
Delivery syst. fault
•
Faulty sensor
•
Check material bunker
•
Check delivery system
•
Have functioning of fill level
sensor checked by a qualified
electrician
F004
Number of igni-
tion attempts
exceeded
•
Ignition fan is faulty
•
Stoker auger is faulty
•
Combustion temperature
sensor is faulty
•
Fill indicator stuck
•
Check ignition fan, stoker
auger and combustion cham-
ber temperature sensor
•
Check material supplies
•
Check delivery auger
•
Check fill level indicator
F005
Grate opens
during
operation
•
Limit switch is faulty or incor-
rectly set
•
Grate motor is faulty
•
Test functioning of limit
switch
•
Test functioning of grate
motor / replace grate motor
F006
Grate blocked up
•
Grate is jammed
•
Limit switch is not correctly
set
•
Limit switch is incorrectly
connected
•
Grate motor is faulty
•
Check grate mechanics
•
Readjust limit switch
•
Have limit switch connection
checked by a qualified electri-
cian
•
Have the grate motor repla-
ced by a heating technician
F007
Lubricating the
feeding
Overcurrent
•
Incorrect parameter setting
•
Rotary feeder is jammed
•
Motor is faulty
•
Check parameter
7-03
•
Check rotary feeder
•
Have a qualified electrician
inspect motor, replace if
necessary
F008
Dosage
Overcurrent
•
Incorrect parameter setting
•
Dosing unit is jammed
•
Motor is faulty
•
Check parameter
7-12
•
Check dosing unit
•
Have a qualified electrician
inspect motor, replace if
necessary
F009
Delivery system
Overcurrent
•
Incorrect parameter setting
•
Delivery system is jammed
•
Motor is faulty
•
Check parameter
7-19
•
Check delivery system
•
Have a qualified electrician
inspect motor, replace if
necessary
No.
Fault
Cause
Remedy
Table 8/1 - Faults
Summary of Contents for Compact 25
Page 1: ...hdg bavaria com HDG Compact 25 80 Operation Manual ...
Page 2: ......
Page 186: ...12 Index 186 HDG Compact 25 35 Version 2 de HDG Bavaria GmbH Oktober 2007 ...
Page 187: ......