6 Using the heating system – Structure of the menus
118
2 - B
OILER
1-26
General information
Mixing valve runtime
Minimum
( 2.0)
2.0s
•
Mixing valve runtime
Setting the minimum runtime of the mixing valve.
1-27
Phase order error
Off
On
•
Phase order
Enables/disables phase order monitoring
No.
Display
Description
Table 6/3 - System level / 1 - General
Warning!
Do not set the maximum boiler temperature above 80 °C.
No.
Display
Description
2-00
Set temp. via
HC ctrl/acc.
Outdoor
External
Outdoor/external
•
Defining the preset boiler temperature
with HDG Hydronic system connected
with variable boiler temp. and external controller
enable via external control and constant boiler tempera-
ture
with external demand and variable boiler temperature
2-01
Terminal 38-39
Demand
Blockage
•
Terminal 38 - 39
Selecting the functions assigned to terminals 38 and 39.
2-02
Boiler
Set temperature
Minimum
( 60)
60°
•
Minimum preset boiler temperature
Minimum target temperature to be preset for the boiler.
(50 - 65°C)
2-03
Boiler
Set temperature
Maximum
( 80)
80°
•
Maximum preset boiler temperature
Specifies the maximum boiler target temperature.
(50 - 80 °C)
2-04
Boiler
Set temperature
Increase
( 5)
5°
•
Preset boiler temperature increased
To achieve the required supply temperature for the loads,
the boiler temperature is increased.
(0 - 10 °C)
2-05
Boiler
Set temperature
Hysteresis
( 5)
5°
•
Boiler hysteresis
The difference between the boiler temperatures to switch
on and to switch off.
(0 - 20 °C)
Table 6/4 - System level / 2 - Boiler
Summary of Contents for Compact 25
Page 1: ...hdg bavaria com HDG Compact 25 80 Operation Manual ...
Page 2: ......
Page 186: ...12 Index 186 HDG Compact 25 35 Version 2 de HDG Bavaria GmbH Oktober 2007 ...
Page 187: ......