WARNING: Disconnect primary power prior to servicing.
Section 3 Operation
ATLAS Analogue
3.9.2
Cooling System Main Menu
The following screen is the Cooling System Main Menu. It shows status, metering and
faults for the cooling system. It also provides for automatic or manual control of pump
switching and tells which pump is active.
3.9.2.1
Cooling System Control Panel
At the bottom of the screen is the Pump Control Panel. This panel would be grayed out
(inactive) for single pump systems. For dual pump systems there are only 2 choices to
be made:
1.
Auto/Manual - This button should always be pressed as shown placing the
pump control in auto-switch mode. In this mode a pump failure will auto-
matically cause a switch to the redundant pump. Manual mode disables the
automatic pump switching.
2.
Pump A/B - This is the manual pump switch control. Press it to switch
pumps.
NOTE:
Pump switching from this control screen will only work if the Pump Control
Panel is in the REMOTE control mode. Placing the Pump Control Panel in
LOCAL mode disables the transmitter pump switching commands. To switch
pumps with the Pump Control Panel in LOCAL mode, press the Pump A or
Pump B switches which are physically located on the Pump Control Panel. For
more information on the Pump Control Panel see "4.6.4 Pump Control Panel" on
page 4-38.
Summary of Contents for ATLAS ANALOGUE
Page 4: ...iv 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 6: ...vi 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 8: ...viii 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 10: ...x 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 14: ...Table of Contents continued 4...