background image

 

 

 

Introduction 

 

1

General safety instructions 

 

2

Device-specific safety 

instructions 

 

3

Appendix 

 

A

List of 

Abbreviations/Acronyms 

 

B

SITRANS 

Pressure transmitter 

Functional safety for SITRANS P, 

series DS III PROFIsafe 

Product information 

07/2006 

A5E00849297-01 

Supplement to the Operating Instructions

Summary of Contents for DS III PROFIsafe Series

Page 1: ...vice specific safety instructions 3 Appendix A List of Abbreviations Acronyms B SITRANS Pressure transmitter Functional safety for SITRANS P series DS III PROFIsafe Product information 07 2006 A5E00849297 01 Supplement to the Operating Instructions ...

Page 2: ...mmissioning and operation of a device system may only be performed by qualified personnel Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission ground and label devices systems and circuits in accordance with established safety practices and standards Prescribed Usage Note the following Warning This device may only be...

Page 3: ...ted system 2 1 2 2 Safety Integrity Level SIL 2 2 3 Device specific safety instructions 3 1 3 1 Application range 3 1 3 2 Safety function 3 2 3 3 Settings 3 3 3 4 Behavior in case of faults 3 4 3 5 Maintenance Checking 3 4 3 6 Safety characteristics 3 5 A Appendix A 1 A 1 Literature and standards A 1 A 2 SIL Declaration of Conformity A 2 A 3 Test report excerpt A 5 B List of Abbreviations Acronyms...

Page 4: ...Table of contents Functional safety for SITRANS P series DS III PROFIsafe iv Product information 07 2006 A5E00849297 01 ...

Page 5: ...t of a safety function This documentation is applicable only in connection with the following documentation No Name Order number 1 Operating Instructions for SITRANS P series DS III PA A5E00053276 1 3 History This history establishes the correlation between the current documentation and the valid firmware of the device The documentation of this edition is applicable for the following firmware Edit...

Page 6: ... course of further development Siemens Regional Offices If you need more information or have particular problems which are not covered sufficiently by the operating instructions contact your local Siemens Regional Office You will find the address of your local Siemens Regional Office on the Internet Product information on the Internet The Programming Manual forms a part of the supplied CD and is a...

Page 7: ... a limit signal sensor and a control valve Definition Safety function Defined function executed by a safety instrumented system with the objective of achieving or maintaining a safe system status taking into account a defined dangerous occurrence Example Limit pressure monitoring Definition Dangerous failure Failure with the potential to bring the safety instrumented system into a dangerous or non...

Page 8: ...itors this value in case it exceeds a preset limit value If a fault occurs the PLC generates a shutdown signal for the connected positioner The positioner switches the corresponding valve to the defined safety position The communication with the positioner via PROFIBUS PA or FOUNDATION Fieldbus remains unrestricted i e position and status messages are still possible 2 2 Safety Integrity Level SIL ...

Page 9: ... 10 5 10 4 3 10 4 10 3 2 10 3 10 2 1 10 2 10 1 The average probability of dangerous failures of the entire safety instrumented system PFDAVG is normally split between the three sub systems in the following figure 6HQVRU H J SUHVVXUH WHPSHUDWXUH HWF RQWURO V VWHP RU ORJLF XQLW H J 3 3 9 FRPSRQHQW LQDO FRQWUROOLQJ HOHPHQW H J YDOYH ZLWK DFWXDWRU DQG SRVLWLRQHU Figure 2 2 Example of PFD distribution ...

Page 10: ...inal controlling elements with complex components if the following conditions are applicable for the device The device is ready for operation The user can configure only the process related parameters e g control range signal direction in case of a fault limiting values etc The configuration level of the firmware is blocked against unauthorized operation The function requires SIL of less than 4 Th...

Page 11: ...ure from the differential pressure breaker range With appropriate parameterization you can also use it for the following additional measurement types Level Volume Mass Flow You can install the transmitter of the appropriate version having the intrinsically safe type of protection EEx ia EEx ib or flameproof enclosure EEx d in hazardous areas on zone 0 and in zones 1 or 2 Devices have an EC type ex...

Page 12: ...lute pressure These versions measure the absolute pressure of corrosive non corrosive and hazardous gases vapors and liquids Requirements These pressure transmitters meet the following requirements Functional safety to SIL 2 under IEC 61508 or IEC 61511 1 from firmware version FW from 301 02 01K Explosion protection for corresponding versions Electromagnetic compatibility in compliance with EN 613...

Page 13: ...nfiguration While operating configuring ensure that the technical data of the pressure transmitter are adhered to in their respective version Checking the safety function We recommend that You check the status for warnings and alarms You check the measured value limits Simulate various measured values and statuses You check the measuring accuracy that must be in the range of 2 for the safety funct...

Page 14: ...te The address of the responsible SIEMENS repair center contacts spare parts lists etc can be found on the Internet See also Services Support http www siemens com automation services support Partner http www automation siemens com partner 3 5 Maintenance Checking Interval We recommend that the functioning of the pressure transmitter be checked at regular intervals of one year Checking the safety f...

Page 15: ...sary for using the system are listed in the SIL declaration of conformity These values apply under the following conditions The SITRANS P pressure transmitter is only used in applications with a low demand rate for the safety function low demand mode The safety related parameters settings have been entered by local operation or PROFIBUS communication before commencing safety instrumented operation...

Page 16: ...Device specific safety instructions 3 6 Safety characteristics Functional safety for SITRANS P series DS III PROFIsafe 3 6 Product information 07 2006 A5E00849297 01 ...

Page 17: ... standards No Standard Description 1 IEC 61508 Section 1 7 Functional safety of following systems Safety instrumented Electrical Electronic Programmable Target group Manufacturers and suppliers of equipment 2 IEC 61511 Section 1 3 Functional safety Safety systems for the process industry Target group Planners constructors and users ...

Page 18: ...Appendix A 2 SIL Declaration of Conformity Functional safety for SITRANS P series DS III PROFIsafe A 2 Product information 07 2006 A5E00849297 01 A 2 SIL Declaration of Conformity ...

Page 19: ...Appendix A 2 SIL Declaration of Conformity Functional safety for SITRANS P series DS III PROFIsafe Product information 07 2006 A5E00849297 01 A 3 ...

Page 20: ...Appendix A 2 SIL Declaration of Conformity Functional safety for SITRANS P series DS III PROFIsafe A 4 Product information 07 2006 A5E00849297 01 ...

Page 21: ...Appendix A 3 Test report excerpt Functional safety for SITRANS P series DS III PROFIsafe Product information 07 2006 A5E00849297 01 A 5 A 3 Test report excerpt ...

Page 22: ...Appendix A 3 Test report excerpt Functional safety for SITRANS P series DS III PROFIsafe A 6 Product information 07 2006 A5E00849297 01 ...

Page 23: ...Appendix A 3 Test report excerpt Functional safety for SITRANS P series DS III PROFIsafe Product information 07 2006 A5E00849297 01 A 7 ...

Page 24: ...Appendix A 3 Test report excerpt Functional safety for SITRANS P series DS III PROFIsafe A 8 Product information 07 2006 A5E00849297 01 ...

Page 25: ...to SIL 4 Each level corresponds to a range of probability for failure of a safety function The higher the Safety Integrity Level of the safety instrumented system the lower the probability that it will not execute the required safety functions SFF Safe Failure Fraction Proportion of safe failures Proportion of failures without the potential to bring the safety instrumented system into a dangerous ...

Page 26: ...List of Abbreviations Acronyms B 1 Abbreviations Functional safety for SITRANS P series DS III PROFIsafe B 2 Product information 07 2006 A5E00849297 01 ...

Page 27: ...n faults failures occur Failure fault Failure A resource is no longer capable of executing a required function Fault Undesired state of a resource indicated by the incapability of executing a required function Fault Failure fault Fault tolerance Fault tolerance N means that a device can execute the intended task even when N faults exist The device fails to execute the intended function in case of ...

Page 28: ...and final controlling element Example A safety instrumented system is made up of a pressure transmitter a limit signal sensor and a control valve Sensor Converter that converts mechanical or other non electrical variables into electrical signals SIL The international standard IEC 61508 defines four discrete Safety Integrity Levels SIL from SIL 1 to SIL 4 Each level corresponds to the probability r...

Page 29: ...1 1 E Electronics 3 5 F Final controlling element 2 1 H History 1 1 M Maintenance 3 4 Mean Time Between Failures 3 3 Measuring accuracy 3 3 More information 1 2 MTTR 3 5 P Product information on the Internet 1 2 S Safety Checking 3 5 Safety function 2 1 3 2 Checking 3 3 3 4 Sensor 2 1 Settings 3 3 Siemens Regional Office 1 2 system Safety instrumented 2 1 T Technical data 3 3 W Write protection 3 ...

Page 30: ...Index Functional safety for SITRANS P series DS III PROFIsafe Index 2 Product information 07 2006 A5E00849297 01 ...