WARNING: Disconnect primary power prior to servicing.
Section 3 Operation
ATLAS Analogue
Figure 3-32 Control Setup Screen
3.9.4.1.1 Touch Screen Calibration
If the touch screen soft buttons on the GUI are working and seem to be accurate, then
this procedure is not required. If the soft buttons on the touch screen do not seem to
work or can only be activated by pressing outside the button graphic, then a simple
touch screen calibration will have to be done as follows:
STEP 1
Go to the touch screen calibration setup screen by pressing the Touch
Cal button in Figure 3-31.
NOTE:
If you are not able to get to the screen, open the control panel and press and hold
the Remote Enable and Disable buttons at the same time and momentarily press
the reset button on the Main Controller. Keep the Enable and Disable buttons
pressed until the display is up and running. After the micro resets, the Main Con-
troller will prompt the operator to calibrate the touch screen.
STEP 2
Once you see the screen in Figure 3-33(a), simply touch the X in the first
2 screens. This will get you to the first screen in Figure 3-34.
STEP 3
To test the calibration simply touch the screen in several places to make
sure an X shows up where you touched (Figure 3-34b).
STEP 4
If the calibration is good, then press ACCEPT. If not, press CANCEL
and the cal procedure will be started over.
To Figure 3-33
To Figure 3-31
Summary of Contents for ATLAS ANALOGUE
Page 4: ...iv 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 6: ...vi 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 8: ...viii 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 10: ...x 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 14: ...Table of Contents continued 4...