1-10
888-2523-001
7/26/05
WARNING: Disconnect primary power prior to servicing.
Section 1 Introduction
ATLAS Analogue
•
Remote
•
Local
•
Interlock
•
Fan A ON
•
Fan B ON
•
*Pump A ON
•
*Pump B ON
•
Pump A Preset
•
Pump B Preset
•
*Coolant Fault
•
*Coolant Low
•
Power
Figure 1-5
Early Model
Cooling System Control Panel
* These status indications are also sent to the transmitter for display on the GUI and via
remote control.
When in Remote mode, the transmitter is responsible for control of the cooling system,
including ON/OFF, manual pump selection and automatic pump switching in the case
of a failure. Placing the control panel in Local mode allows manual switching of the
pumps using the pump select buttons on the cooling control panel.
The lower half of the control panel contains the AC isolation switch which disconnects
AC power from the pump module and heat exchanger as well as the control circuitry in
the control panel itself. The control panel should be mounted within eyesight of the
transmitter (usually next to the transmitter disconnect panel).
1.2.6.2
Pump Module
The pump module is a self-contained unit with a storage tank, pressure and temperature
gauges, a strainer filter and dual pumps operating in main/standby mode. The pump
module is designed for outside mounting.
Summary of Contents for ATLAS ANALOGUE
Page 4: ...iv 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 6: ...vi 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 8: ...viii 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 10: ...x 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Page 14: ...Table of Contents continued 4...