6LE007317A
58
RS485
Interface type
2 to 3 half duplex wires
Protocol
MODBUS RTU
Baudrate
programmable 1200 … 115200 bps
Function
Configuration and data reading
Isolation
Functional
Maximum distance
1200 m @9600 baud
200 m @115200 baud
Termination
internal 120 ohms (selectable DIP switch)
Environmental specifications
Ambient operating temperature
-30º … +70º C
Storage temperature
-40º … +70º C
Operating humidity
55ºC / 95 % HR
Operating altitude
< 2000 m
Vibrations
IEC 60947-1
Shocks
shocks according to Annex Q IEC 60947-1
EMC classification
Class A+B
Insulation / Overvoltage cat.
Impulse V withstand
Uimp = 4 kV. Test = 8 kV between sources / 6 kV between phases
Installation overvoltage category
OVC III
Degree of pollution
Pollution degree 3
USB
Connection
USB 2
Type
Type B Micro USB
Mechanical characteristics
Height*length*depth
240x180x64 mm
Weight
1085 g
Event recorder
Capacity
300 100 alarms
Data storage
non-volatile memory
Type tests - All the EMC tests are described in the sequence 4 947-1
Electrostatic Discharge Immunity - Air
8 kV (B)
Electrostatic Discharge Immunity - Direct
4 kV (B)
Radiated RF Immunity
10 V/m
Electrical Fast Transient / Burst Immunity
2 kV power access, 1 kV signal access
Surge Immunity
1 kV diff
Conducted RF Immunity
10 Vrms
Radiated RF Emisison
Class B
Conducted RF Emission
Class B
Case
Fire reaction of housing and cover
self-extinguishing UL94-V0
Service life components
MTBF
> 100 years