6LE007317A
34
Balanced network
Unbalanced network
For each parameter, the limits can be set in % vs the nominal value and there are two parameters to set: the tripping value that will
make the source be considered unavailable (FAIL) and the value that will make the source be considered available again (RESTORE).
The thresholds and hystereses are defined as percentages of nominal voltage.
The hystereses define return to normal levels following an under-voltage or over-voltage.
Checked value (voltage)
%
100
T
Source available
Upper threshold (OV FAIL)
Lower threshold (UV FAIL)
Upper threshold hysteresis
(OV RESTORE)
Lower threshold hysteresis
(UV RESTORE)
In order to save the settings it’ s mandatory to select
SAVE CONFIG on the bottom of the screen or press
OK button for 1.5 s and a pop-up will appear asking for
confirmation before “SAVE AND QUIT ?”.
Definition
** Adjustment Range
OV FAIL
115% Overvoltage threshold: Source 1
102 … 130%
OV RESTORE
110% Over-voltage hysteresis: Source 1
101 … 129%
UV FAIL
085% Undervoltage threshold: Source 1
60 … 98%
UV RESTORE
095% Undervoltage hysteresis: Source 1
61 … 99%
UB FAIL
000% Phase unbalance threshold: Source 1
Refer to next paragraph for further details
0 … 30%
UB RESTORE
000% Hysteresis unbalance threshold: Source 1
Refer to next paragraph for further details
0 … 29%
OF FAIL
105% Over Frequency Threshold: Source 1
102 … 130%
OF RESTORE
103% Over Frequency Hysteresis: Source 1
101 … 129%
UF FAIL
095% Under Frequency Threshold: Source 1
60 … 98%
UF RESTORE
097% Under Frequency Hysteresis: Source 1
61 … 99%
** Adjustment range given:
As a % of U nominal for Over and Undervoltage
As a % of U avg in case of unbalances.
As a % of nominal frequency
U 13
3
U 32
U 21
3’
U 1’3’
U 3’2’
N’
N
2’
U 2’1’
1’
1
2
3
1