6LE007317A
55
PRI
CHANGE PRIO
Changes the priority between sources
SS1
BYPASS STAB S1
Bypasses the stabilisation timer for S1
SS2
BYPASS STAB S2
Bypasses the stabilisation timer for S2
ALE
EXT ALARM
External alarm active. It will be logged in the alarm log as External Alarm and the Alarm LED will be active. The
alarm will be In progress until input is cleared
FTE
EXT FAULT
External fault active. The product will transfer to position 0 / center off. CTRL is permitted. Mode will be inhibit.
Genset will not start if source is lost. "EXTERNAL FAULT" will be displayed on screen. It will be logged in the fault
log as External Fault and the Fault LED will be active. The fault will be In progress until input is cleared and fault
reset.
MSR
PRIO TEST ON LOAD
EJP / Stay on "backup" source. Priority Test on Load. Order to stay in S2 even if the source is lost or
unavailable.
OA1
FORCE S1 AVAIL.
Force Source 1 as Available
OA2
FORCE S2 AVAIL.
Force Source 2 as Available
OU1
FORCE S1 UNAVAIL.
Force Source 1 as Unavailable
OU2
FORCE S2 UNAVAIL.
Force Source 2 as Unavailable
RST
RST FAULT STATE
Fault Reset:
This input may be used to reset a fault condition after the fault has been cleared. Faults may also be reset
through communication or through the display.
CHP
CHANGE PRIO
Changes the position (if no priority defined). It partially inhibits when active. It goes back to Auto when cleared.
It has to be a permanent maintained input, it can't be an impulse.