6LE007317A
14
All inputs and outputs can be configured and functions can be changed by going in the Parameters / I/O menu of the controller.
For the cabling, please consider the following table of functioning:
Cabling Output relays 1-4
Cabling Output Latching relays 5 & 6
Controller config
STATE (relay)
Normally
Open (NO) (11-14)
Normally
Closed (NC) (11-12)
Normally
Open (NO) (61-64)
Normally
Closed (NC) (61-62)
Output configured as NO
NO by default
OFF (not active)
Open
Closed
Open
Closed
ON (activated by firmware)
Closed
Open
Closed
Open
Controller not supplied
Open
Closed
Closed*
Open*
Output configured as NC
OFF (not active)
Closed
Open
Closed
Open
ON (activated by firmware)
Open
Closed
Open
Closed
Controller not supplied
Open
Closed
Closed*
Open*
* HZI855 controller includes two bi-stable relays with backup energy, when the controller loses all sources of power supply outputs 5 and 6 will automatically
activate (NO contact will close and NC contact will open). This is a safety feature designed to ensure power availability to the load in Main-Genset or Genset-Genset
application by forcing generators to start in case of total power loss. It is highly recommended to configure the outputs 5 and 6 to take benefit from this function.