H2flow Controls
ProcessDefender™
67
Parameter List
H2flow Controls
ProcessDefender™
66
Parameter List
Display I.D.
Function
Display Text
Range
Default
Symbol
5.2.0
Response delay
“RES.DEL”
5.2.1
Configure response delay overload
0.5-255
0.5
S
5.2.2
Configure response delay underload
0.5-255
0.5
S
5.3.0
Relay 3 latch
“R3 LAT”
5.3.1
Configure relay 3 Latch reset
“ON” or “OFF”
“OFF”
5.3.2
Configure relay 3 hysteresis %
0-50
0
%
5.3.3
Configure as normally closed or normally open
“NC” or “NO”
“NO”
6.0.0
Inputs / Outputs
“IN/OUT”
6.1.0
Digital input
“DIG IN”
6.1.1
Digital input, autoset trigger
“ON” or “OFF”
“OFF”
6.2.0
Analog output
“A OUTS”
6.2.1
Configure analog output source (measured power in percent of rated power)
“PCT”
“PCT”
6.2.2
Configure range 4mA
0-999
0
%, KW, HP
6.2.3
Configure range 20mA
0-999
100
%, KW, HP
6.3.0
Modbus
“MODBUS”
6.3.1
Configure modbus baud rate
“4800”, “9600”, “14400”, “19200”, “24000”,
“28800”,
“33600”, “38400”, “43200”, “48000”, “52800”,
“57600”, “62400”, “67200”, “72000”, “76800”,
“81600”, “86400”, “91200”, “96000”, “100800”,
“105600”, “110400”, “115200”, “120000”,
“124800”,
“129600”, “134400”, “139200”, “144000”,
“148800”,
“153600”, “158400”, “163200”, “168000”,
“172800”,
“177600”, “182400”, “187200”, “192000”
“9600”
6.3.2
Configure modbus parity, 2 stop - no parity, 1 stop - even parity, or 1 stop -
odd parity
“2S-NP”, “1S-EP” or “1S-OP”
“2S-NP”
6.3.3
Configure modbus I.D.
0-255
10
7.0.0
Advanced settings
“ADV. SET”
8.0.0
System settings
“SYSTEM”
8.1.0
Factory reset
“F RESET”
8.1.1
Enter passcode “369”
000-999
369
Lock symbol
8.1.2
Apply factory defaults
“NO” or “YES”
“NO”