H2flow Controls
ProcessDefender™
61
Parameter List
H2flow Controls
ProcessDefender™
60
Parameter List
Display I.D.
Function
Display Text
Range
Default Symbol
Measured power in % of rated power
0-999
%
Measured power in kW
0.00-999.0
KW
Measured power in HP
0.0-999.0
HP
Measured line voltage
0-528
V
Measured current
0.0-999A
A
1.0.0
Autoset
“AUTO”
1.1.0
Choose auto setup setting
“A.SET”
1.1.1
Select Autoset mode
“BOTH”, “OVER” or “UNDER”
“BOTH”
1.1.2
Max main margin (Relay 1) Sensor alarm 1
“MAX M”
0-50
20
%
1.1.3
Max pre margin (Relay 2) Sensor alarm 3
“MAX P”
0-50
10
%
1.1.4
Min pre margin (Relay 2) Sensor alarm 4
“MIN P”
0-50
10
%
1.1.5
Min main margin (Relay 1) Sensor alarm 2
“MAX M”
0-50
20
%
1.1.6
Apply Autoset?
“YES” or “NO”
“YES”
2.0.0
Configuration
“CONFIG”
2.1.0
Parameter lock/unlock
“PAR.LOK”
2.1.1
Parameter lock/unlock code
000-999
369
Lock symbol
2.2.0
Rated Motor Power
“MOTOR”
2.2.1
Choose kW or HP
“KW” or “HP”
“KW”
KW/HP
2.2.2
Configure rated motor power kW
0.1-745
2.2
kW/W
2.2.2
Configure rated motor power HP
0-999
HP
2.3.0
Start delay
“ST DEL”
2.3.1
Configure start delay
0-255
2
S
2.4.0
Primary CT current
“P.CT.AMP”
2.4.1
Configure primary CT current
5-1000
5
A
2.5.0
Number of turns of the primary wire through the CT
“TP CT”
2.5.1
Turns value
1-10
1
8. parameter list