Menu 2.3.1 - Motor Start Delay
Menu 2.3.1 relates to the Motor Start Delay. The time should be set long enough to
allow the motor to reach full speed and for the driven equipment to be under normal
load. For example, if the motor is driving a self-priming pump, the time delay should
be set long enough for the motor to start and the pump to be primed. However, please
note that the PD100 will not enable any of its process protection features until this
time period expired.
Fig.2.5
Fig.2.6
Fig.2.7
From menu 2.3.0, press the
button to enter the sub-menu 2.3.1.
In Fig.2.6 (above), the screen shows the factory default Start Delay time of two
(2)-seconds.
To adjust this value, press the
or
button. The display will now appear as seen
in Fig.2.7 (above). Using the same procedure as described for 2.2.2, adjust the time to
that required for the Motor Start Delay. Press the
button to confi rm your setting.
The display will show ‘SAVED’ for two-seconds and automatically move to menu 2.4.1.