H2flow Controls
ProcessDefender™
65
Parameter List
H2flow Controls
ProcessDefender™
64
Parameter List
Display I.D.
Function
Display Text
Range
Default
Symbol
3.3.3
Configure as normally closed or normally open
“NC” or “NO”
“NC”
4.0.0
Pre alarm, relay 2
“PRE R2”
4.1.0
Pre alarm settings
“PRE.SET”
4.1.1
Configure
“OVER”, “UNDER”, “BOTH”
or “OFF”
“OFF”
4.1.2
Configure max trigger point, as percent of motor rated input power. (Only
show selected monitor source)
“MAX P”
0-150
100
%
Configure max trigger point, as measured input power in kW. (Only show
selected monitor source)
0.0-745.0
0
kW
Configure max trigger point, as measured input power HP. (Only show
selected monitor source)
0-999
0
HP
4.1.3
Configure min trigger point, as percent of motor rated input power. (Only
show selected monitor source)
“MIN P”
0-150
0
%
Configure min trigger point, as measured input power in kW. (Only show
selected monitor source)
0-745
0
kW
Configure min trigger point, as measured input power HP. (Only show
selected monitor source)
0-20
0
HP
4.2.0
Response delay
“RES/DEL”
4.2.1
Configure response delay overload
0.5-255
0.5
S
4.2.2
Configure response delay underload
0.5-255
0.5
S
4.3.0
Relay 2 latch
“R2 LAT”
4.3.1
Configure relay 2 Latch reset
“ON” or “OFF”
“ON”
4.3.2
Configure relay 2 hysteresis %
0-50
0
%
4.3.3
Configure as normally closed or normally open
“NC” or “NO”
“NO”
5.0.0
General alarm, relay 3
“GEN R3”
5.1.0
Monitor function
“GEN SET”
5.1.1
Configure
“OVER”, “UNDER”,
“BOTH” or “OFF”
“OFF”
5.1.2
Configure source as percent of motor rated input power, measured input power in kW,
measured input power HP or voltage
“VOLT”
“VOLT”
5.1.3
Configure max trigger point, as percent of operating voltage
“MAX G”
0-255
110
%
5.1.4
Configure min trigger point, as percent of operating voltage
“MIN G”
0-255
95
%