78 Smart Climate 310 rev. 03
Adjusting the Static Pressure Compensation Value
Select the opening that must be added or removed when a
pressure compensation is applied on an air inlet. This parameter
ranges from 0 to 10% and must be set separately for each inlet. To
deactivate an inlet, set the value to Off.
To adjust the SP compensation value, proceed as follows:
1. Select the desired air inlet:
Air Inlet 1, Air Inlet 2
or
0-10V
Output
(0-10V air inlet).
The following parameters do not apply to 0-10V chimney dampers.
2. Press the down-arrow key to display
the Stat. P Compens
parameter.
This parameter is accessible if the static pressure compensation
option is enabled in the USER SETUP.
3. Press
Adjust
. The compensation value flashes on the
display.
4. Use the arrow keys to set it to the desired value.