44 Smart Climate 310 rev. 03
Adjusting the Starting Temperature for 0-10V
Outputs
When it is used for ventilation, the 0-10V output starts running
when the room temperature reaches its start temperature. This
temperature can be set as an absolute value or it can be related to
the set point, which means it is automatically adjusted when the set
point changes (refer to the User Setup to set this option).
The start temperature can be adjusted from -40 to 120°F (-40 to
48.9°C).
To select the starting temperature of the 0-10V Output, proceed as
follows:
1. Press
0-10v Output.
The start temperature of the 0-
10V output is displayed.
Make sure the 0-10V is used for ventilation (see User Setup menu).
2. Press
Adjust
. The start temperature flashes on the
display.
3. Use the arrow keys to set it to the desired value.
Selecting the Minimum and Maximum Speeds
for 0-10V Outputs
The minimum and maximum speeds of the 0-10V fan output can
be adjusted from 0 to 100%.
1. Press
0-10v Output
.
Make sure the 0-10V is used for ventilation in the User Setup menu.
2. Press the down-arrow key to select
the Min/Max
speed
display.
3. Press
Adjust
then use the arrow keys to set the
minimum speed to the desired value.
4. Press
Adjust
once again, the maximum speed flashes
on the display. Use the arrow keys to set it to the
desired value.
Summary of Contents for Smart Climate 310
Page 1: ...Smart Climate 310 User s Guide 895 00676 REV 04 890 00582 REV 03...
Page 96: ...96 Smart Climate 310 rev 03 Probe Assignment...
Page 97: ...Smart Climate 310 rev 03 97 User Setup Menu...
Page 98: ...98 Smart Climate 310 rev 03...
Page 101: ...Smart Climate 310 rev 03 101 3 Press on the card and make it clip to the main board...
Page 102: ...102 Smart Climate 310 rev 03...