Reverse osmosis system
GENO-OSMO-X
Order no.
134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
15
3 | Technical specifications
Table C-1: Technical specifications
Reverse osmosis system GENO-OSMO-X
200
400
800
1200 1600 2200
3000
Connection data
Nominal connection diameter (male thread)
of feed water inlet
1“
1“
1“
1“
1“
1 ¼“
1 ¼“
Nominal connection diameter (male thread)
of permeate outlet
1“
1“
1“
1“
1“
1“
1“
Nominal connection diameter (male thread)
of concentrate outlet
1“
1“
1“
1“
1“
1“
1“
Min. drain connection
Without optional AVRO
DN 50
DN 50
DN 50
DN 50
DN 50
DN 50
DN 50
With optional AVRO
DN 50
DN 50
DN 50
DN 100 DN 100
-
-
Power supply
[V/Hz]
3/N/PE, 400 V/50...60 Hz
Min. power outlet provided on site
5.5 kW / C 20 A / 2.5 mm²
Protection/protection class
IP 54/
Power input in case of unpressurised delivery of the permeate into a tank at a switching frequency of the frequency
converter of 8 kHz and an inlet pressure of 4 bar in the feed water
Recovery of 80 %
[kW]
0.53
0.87
0.94
1.40
1.74
2.10
2.30
Recovery of 50 %
[kW]
0.53
0.88
0.94
1.30
1.60
-
-
Power input if the permeate is delivered directly to the consumers with a supply pressure of 3.8 bar at a switching
frequency of the frequency converter of 8 kHz and an inlet pressure of 4 bar in the feed water.
Recovery of 80 %
[kW]
0.86
1.44
1.60
2.00
2.31
2.30
2.80
Recovery of 50 %
[kW]
0.81
1.20
1.41
1.90
2.11
-
-
Performance data
Permeate capacity at a
Feed water temperature of 10 °C
[l/h]
170
340
680
1020
1360
1870
2550
Feed water temperature of 15 °C
[l/h]
200
400
800
1200
1600
2200
3000
Feed water temperature of 15 °C
[m³/d]
4.8
9.6
19.2
28.8
38.4
52.8
72.0
Min. inlet flow pressure of feed water
[bar]
2.5
Min. outlet pressure of permeate
[bar]
0.5
Nominal pressure
PN 16
Salt rejection
95 – 99 %
Total salt concentration in the feed wa-
ter as NaCl, max.
[ppm]
1000
Recovery min./max.
[%]
50-80 (adjustable)
65-80 (adjustable)
Volume flow concentrate to drain at a
recovery of 80%. (at 15°C)
[l/h]
50
100
200
300
400
550
750
Feed water volume flow (15 °C)
drain at a recovery of 80%.
[l/h]
250
500
1000
1500
2000
2750
3750
Filling volumes and consumption data
Number of modules (size 4")
[pcs.]
½
1
2
3
4
6
8
Dimensions and weights
System width
[mm]
900
900
1035
1035
1170
1170
1170
System height
[mm]
1700
1700
1700
1700
1700
1700
1700
System depth
[mm]
675
675
675
675
675
675
675
Room height/installation height, min.
[mm]
1800
1800
1800
1800
1800
1800
1800
Operating weight, approx.
[kg]
100
115
145
170
195
240
290
General
Feed water temperature, min./max.
[°C]
10/30
1)
Ambient temperature, min./max.
[°C]
5/35
Order no.
750 200
750 210 750 220 750 230 750 240 750 250 750 260
1)
For temperatures of feed water > 20 °C a separate configuration of the system is required.