Reverse osmosis system
GENO-OSMO-X
Order no.
134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
29
4.3 Connections within the GENO-OSMO-X reverse osmosis system
The following connections are preset internally at the factory and
must not be modified:
From
GENO-OSMO-X
control unit
to component
Line
Signal
1
Mains switch housing lid
H05VV-F 5G1.5 mm²
L
From mains
switch
2
N
3
L
To mains
switch
4
N
PE
PE
5
230 V~ feed from
power distribution
RO1E2
38
H05VV-F 3G0.75 mm²
L
6
39
N
PE
40
PE
12
Frequency converter
of high-pressure pump
RO1P1A1
1
LiYcY 7x0.25 mm²
+ 24 V=
WH
Release FU
13
2
IN
BN
56
10
+ 24 V=
GY
Fault signal
FU (
57
11
DI 6
PK
40
6
4-20 mA
YE
Desired value
FU
41
7
GND
GN
PE
Shield
20
Feed water solenoid valve
RO1V1
H05VV-F 2x0.5 mm²
+ 24 V= (clocked for power reduction
21
GND
28
Regulating valve concentrate
to drain
RO1V3
(step motor)
LiYY 7x0.25 mm² (blue
strand is not used)
Ph1
GN
29
Ph1
WH
30
Com1
BN
31
Ph2
PK
32
Ph2
YE
33
Com2
GY
34
Regulating valve concentrate
recirculation
KR RO1V2
(step motor)
LiYY 7x0.25 mm² (white
strand is not used)
Ph1
GN
35
Ph1
BU
36
Com1
BN
37
Ph2
PK
38
Ph2
YE
39
Com2
GY
42
Temperature measurement
RO1CT1
LiYcY 4x0.25 mm²
Pt 100
BN
43
GN
PE
Conductivity measuring cell
RO1CQ1
cell constant 0,1
K= 0.1 1/cm
Shield
44
WH
45
YE
46
Conductivity measuring cell
RO1CQ1
cell constant 0,1
LiYcY 4x0,25 mm²
K= 0,1 1/cm
47
WH
YE
54
Pressure switch for minimum
pressure
RO1CP1
LiYY 2x0.5 mm²
+ 24 V=
WH
55
DI 5
BN
58
Pressure switch for maximum
pressure
RO1CP3
LiYY 2x0.5 mm²
+ 24 V=
WH
59
DI 10
BN
73
Feed water flow sensor
RO1CF1
LiYY 3x0.25 mm²
+12 V=
WH
74
[pulse]
GN
75
GND
BN
76
Flow sensor Feed
RO1CF2
LiYY 3x0.25 mm²
+12 V=
WH
77
[pulse]
GN
78
GND
BN
79
Flow sensor ermeate
RO1CF3
LiYY 3x0.25 mm²
+12 V=
WH
80
[pulse]
GN
81
GND
BN
Summary of Contents for GENO-OSMO-X
Page 2: ......