Reverse osmosis system
GENO-OSMO-X
Order no.
134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
63
Continuation table G-1: Warnings
This is what you observe
This is the cause
This is what to do
W037
Stop filter sys. or overfill safety
BB1
Tank has reached max. filling
level.
Check filling level in tank and regu-
late, if necessary.
W038
Comm. error MK200 12RA
Bus connection to MK200 12RA
module disturbed.
Check bus cabling and restore, if
necessary.
W039
Error KK200 12RA defective
MK200 12RA module disturbed.
Check setting at the module, check
parametrisation.
W040
Comm. error MK200 4AA
Bus connection to MK200 4AA
module disturbed.
Check bus cabling and restore, if
necessary.
W041
Error MK200 4AA defective
MK200 4AA module disturbed.
Check setting at the module, check
parametrisation.
W053
Communication error
basic circuit board
Faulty connection between touch
panel GENO-tronic and basic cir-
cuit board.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
W055
Firmware basic circuit board out
of date
Firmware basic circuit board out
of date
Software version of operating ele-
ment does not match with the basic
circuit board
W056
SD card removed
SD card missing, defective.
Insert/replace SD card.
W057
SD card full
Memory of SD card full.
Replace SD card.
W058
SD card E/A error
SD card defective.
Replace SD card.
W060
EH (water softener) lack of salt
Not enough salt in brine tank.
Check salt level in brine tank and re-
fill salt tablets as per DIN EN 973 A,
if necessary.
W061
EH (water softener) service in-
terval
Maintenance interval of water sof-
tener has expired.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
W062
DEA (pressure booster system)
service interval
Maintenance interval of pressure
booster system has expired.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
W063
DEA ext. release signal lacking
Release signal selected incor-
rectly.
Check parameter settings.
W064
DEA dry-run protection
Not enough water in the supply
tank.
Signal acknowledges itself as soon
as sufficient water is available again.
W065
DEA power failure
Power failure >1 minute.
Check parameter setting in operator
menu. Ensure power supply.