DC INVERTER MULTI VRF CONTROL
77
2. When ADDRESS SETTING is blinking, press SELECT button into address setting interface.
Press LEFT or RIGHT button to switch between SOFT and Hard ADDRESS settings, and UP or Down button
to adjust their values
。
After adjustment, press CONFIRM button to make the address values corresponding and
effective. If the cursor stops at hard address position (hard address is blinking), press CANCEL button to make the
setting value ineffective, in which case, the “- -”will be displayed.(Soft address is the No. displayed in 1-64 grid of
LCD and hard address is the actual one of communication module.)
In this example, the centralized controller controls 3 communication modules with the address of 01, 02 and 03
(i.e. hard address is 01,02 and 03).For convenient management, soft address will be set to the same as hard address, i.e.
“01 001”,“02 002”and “03 003”.
If communication is normal after setting, the centralized controller will display as the following figure:
I.
01,02 and 03 of soft address is displayed, which indicates normal communication of these 3
communication modules.
II.
PRESENT UNIT NO. displays “01-08”, which indicates No. 08 indoor unit under 01 communication
module is being checked.
III.
Press ROOM/REGION button to check other indoor units’ status under present communication module.
Indoor units’ status is automatically detected, without setting in centralized controller.
Step 5: Troubleshooting during Installation of Centralized Controller
Generally speaking, connection of communication lines, address DIP of communication module and address
mapping setting of centralized controller are the common problems during installation of centralized controller. These
problems can be reflected from running indicator (green) of communication module. Meanwhile, it is recommended to debug
the centralized controller after making communication of outdoor and indoor units smooth to simplify the problems.
A. Connection of communication lines
Soft address
Hard address
Soft address
display 01,02
and 03
Press this button to
check indoor unit status
under
corresponding
soft address.
Summary of Contents for GMV(L)-Pd100W/NaB-K
Page 1: ...1 DC INVERTER MULTI VRF Service Manual GREE ELECTRIC APPLIANCES INC OF ZHUHAI ...
Page 4: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 1 PRODUCT ...
Page 40: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 37 CONTROL ...
Page 41: ...DC INVERTER MULTI VRF CONTROL 38 CONTROL 1 OPERATION FLOWCHART ...
Page 43: ...DC INVERTER MULTI VRF CONTROL 40 1 2 Heating Operation ...
Page 70: ...DC INVERTER MULTI VRF CONTROL 67 2 Frame Diagram of System Net 上 WC ...
Page 90: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 87 INSTALLATION ...
Page 115: ...DC INVERTER MULTI VRF INSTALLATION 112 ...
Page 159: ...DC INVERTER MULTI VRF MAINTENANCE 156 MAINTENANCE ...
Page 179: ...DC INVERTER MULTI VRF MAINTENANCE 176 ...
Page 212: ...DC INVERTER MULTI VRF MAINTENANCE 209 2 GMV L R90T Na K GMV L R112T Na K GMV L R125T Na K ...
Page 216: ...DC INVERTER MULTI VRF MAINTENANCE 213 2 GMV L R40P Na K GMV L R45P Na K GMV L R50P Na K ...
Page 224: ...DC INVERTER MULTI VRF MAINTENANCE 221 2 GMV L R36G NaB K GMV L R45G NaB K ...
Page 226: ...DC INVERTER MULTI VRF MAINTENANCE 223 3 GMV L R50G NaB K GMV L R56G NaB K ...
Page 228: ...DC INVERTER MULTI VRF MAINTENANCE 225 4 GMV L R71G Na K GMV L R80G Na K ...
Page 230: ...DC INVERTER MULTI VRF MAINTENANCE 227 5 GMV L R22G NaC K GMV L R28G NaC K ...
Page 232: ...DC INVERTER MULTI VRF MAINTENANCE 229 6 GMV L R36G NaC K GMV L R45G NaC K ...
Page 237: ...DC INVERTER MULTI VRF MAINTENANCE 234 2 GMV L R71Zd Na K ...
Page 240: ...DC INVERTER MULTI VRF MAINTENANCE 237 3 GMV L R90Zd Na K GMV L R112Zd Na K GMV L R125Zd Na K ...