DC INVERTER MULTI VRF INSTALLATION
144
18). All the condensate pipes must be installed at a distance over 500mm from the electric
box of the unit.
8.3 Installation of drainage hose for different types of indoor unit
1) Duct-type Indoor Unit (Including General Static Pressure and Low Static Pressure)
a. Installation of drainage hose
The diameter of drainage hose shall be equal to or higher than the diameter of
connection pipe. (PVC pipe: Dimension: Outer diameter 25mm, 32mm)
The drainage hose shall be short and has a down gradient of 1/100 at least, thus to
avoid air bag.
To ensure that the drainage hose will not be bent and has enough gradient, a distance of
1 ~ 1.5m shall be kept between the hanger frames.
Use drainage hose and clamp.
Insert the drainage hose to the root. From the middle of white tape, tighten the clamp until the
tightening distance to the screw head is shorter than 4mm.
A. For thermal isolation, use sealing tape to wrap the drainage hose and clamp.
B. The indoor drainage hose shall be thermally insulated.
C. To prevent foreign articles from entering the pipe, please minimize the bend of pipeline, thus
to ensure cleanliness of the drainage elbow.
D. The drainage hose must be wrapped with thermal insulation tube, thus to avoid
condensing on the outer surface of drainage hose . See below for the thickness of thermal
insulation tube.
Gradient over 1/100
Clamp
Sponge (grey)
Drainage hose
Big sponge (accessory)
Clamp (accessory)
Below 4mm
Summary of Contents for GMV(L)-Pd100W/NaB-K
Page 1: ...1 DC INVERTER MULTI VRF Service Manual GREE ELECTRIC APPLIANCES INC OF ZHUHAI ...
Page 4: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 1 PRODUCT ...
Page 40: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 37 CONTROL ...
Page 41: ...DC INVERTER MULTI VRF CONTROL 38 CONTROL 1 OPERATION FLOWCHART ...
Page 43: ...DC INVERTER MULTI VRF CONTROL 40 1 2 Heating Operation ...
Page 70: ...DC INVERTER MULTI VRF CONTROL 67 2 Frame Diagram of System Net 上 WC ...
Page 90: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 87 INSTALLATION ...
Page 115: ...DC INVERTER MULTI VRF INSTALLATION 112 ...
Page 159: ...DC INVERTER MULTI VRF MAINTENANCE 156 MAINTENANCE ...
Page 179: ...DC INVERTER MULTI VRF MAINTENANCE 176 ...
Page 212: ...DC INVERTER MULTI VRF MAINTENANCE 209 2 GMV L R90T Na K GMV L R112T Na K GMV L R125T Na K ...
Page 216: ...DC INVERTER MULTI VRF MAINTENANCE 213 2 GMV L R40P Na K GMV L R45P Na K GMV L R50P Na K ...
Page 224: ...DC INVERTER MULTI VRF MAINTENANCE 221 2 GMV L R36G NaB K GMV L R45G NaB K ...
Page 226: ...DC INVERTER MULTI VRF MAINTENANCE 223 3 GMV L R50G NaB K GMV L R56G NaB K ...
Page 228: ...DC INVERTER MULTI VRF MAINTENANCE 225 4 GMV L R71G Na K GMV L R80G Na K ...
Page 230: ...DC INVERTER MULTI VRF MAINTENANCE 227 5 GMV L R22G NaC K GMV L R28G NaC K ...
Page 232: ...DC INVERTER MULTI VRF MAINTENANCE 229 6 GMV L R36G NaC K GMV L R45G NaC K ...
Page 237: ...DC INVERTER MULTI VRF MAINTENANCE 234 2 GMV L R71Zd Na K ...
Page 240: ...DC INVERTER MULTI VRF MAINTENANCE 237 3 GMV L R90Zd Na K GMV L R112Zd Na K GMV L R125Zd Na K ...