DC INVERTER MULTI VRF CONTROL
43
Shown as the following figure:
3) Outdoor fan control
Definition of fan speed: Ultra-high fan speed: the upper and lower fans are both at high speed; High fan speed:
the upper and lower fans are both at medium speed; Medium fan speed: the upper and lower fan are both at low
speed; Low fan speed: the upper fan is at low speed, the lower fan stops; Stop fan speed: both the upper and lower
fans stop.
◆
Cooling Mode:
The fan could be switched among ultra-high - high - medium - low fan speed.
The compressor should be forced to run at high fan speed for 35 seconds before started. After the compressor
started, you should not stop it within 3 minutes, but you could regulate it up to ultra-high fan speed. The discharge
pressure should be measured 3 minutes later, and you can regulate the fans’ speed according to the following
discharge pressure:
Absolute pressure
value for discharge
(℃)
P
≤
30
℃
30
℃<
P
≤
42
℃
42
℃<
P
≤
49
℃
P
>
49
℃
Cooling
Shutdown the
fan forcibly
Turn down one
grade (not including
stopping
windshield )
Remain
Turn up one
grade
For ultra-high fan speed, you couldn’t turn up the grade anymore;
◆
Heating Mode:
The fan should run at high fan speed for 35s before the compressor is started, meanwhile, it is not allowed to turn
up to ultra-high fan speed within the earlier 3 minutes after the compressor started, but it could be switched to low
speed and stopping fan. You could turn up to the highest level ultra-high fan speed after 3 minutes.
Pressure section:
Absolute pressure value
for discharge
(℃)
P
≤
37
℃
37
℃<
P
<
48
℃
P
≥
48
℃
Heating
Turn up one grade
Remain
Turn down one grade
4) Defrosting Function
◆
Defrosting Start Conditions
Keep heating (the four-way valve is under the heating position) for 50 minutes; when the intermediate sensor
temperature and outdoor ambient temperature retain the following curve figure for 120s,
Frequency Initialization pause point
Inverter controller
4-way Valve
Fan
Outdoor unit EXV
Indoor unit EXV 0- step
To the target frequency
Regulate according to
normal logic
Initialization
250-step
Power the four-way valve if the high and low voltage
deviation is no less than 3kg/cm2G
Initialization
350-step
Summary of Contents for GMV(L)-Pd100W/NaB-K
Page 1: ...1 DC INVERTER MULTI VRF Service Manual GREE ELECTRIC APPLIANCES INC OF ZHUHAI ...
Page 4: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 1 PRODUCT ...
Page 40: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 37 CONTROL ...
Page 41: ...DC INVERTER MULTI VRF CONTROL 38 CONTROL 1 OPERATION FLOWCHART ...
Page 43: ...DC INVERTER MULTI VRF CONTROL 40 1 2 Heating Operation ...
Page 70: ...DC INVERTER MULTI VRF CONTROL 67 2 Frame Diagram of System Net 上 WC ...
Page 90: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 87 INSTALLATION ...
Page 115: ...DC INVERTER MULTI VRF INSTALLATION 112 ...
Page 159: ...DC INVERTER MULTI VRF MAINTENANCE 156 MAINTENANCE ...
Page 179: ...DC INVERTER MULTI VRF MAINTENANCE 176 ...
Page 212: ...DC INVERTER MULTI VRF MAINTENANCE 209 2 GMV L R90T Na K GMV L R112T Na K GMV L R125T Na K ...
Page 216: ...DC INVERTER MULTI VRF MAINTENANCE 213 2 GMV L R40P Na K GMV L R45P Na K GMV L R50P Na K ...
Page 224: ...DC INVERTER MULTI VRF MAINTENANCE 221 2 GMV L R36G NaB K GMV L R45G NaB K ...
Page 226: ...DC INVERTER MULTI VRF MAINTENANCE 223 3 GMV L R50G NaB K GMV L R56G NaB K ...
Page 228: ...DC INVERTER MULTI VRF MAINTENANCE 225 4 GMV L R71G Na K GMV L R80G Na K ...
Page 230: ...DC INVERTER MULTI VRF MAINTENANCE 227 5 GMV L R22G NaC K GMV L R28G NaC K ...
Page 232: ...DC INVERTER MULTI VRF MAINTENANCE 229 6 GMV L R36G NaC K GMV L R45G NaC K ...
Page 237: ...DC INVERTER MULTI VRF MAINTENANCE 234 2 GMV L R71Zd Na K ...
Page 240: ...DC INVERTER MULTI VRF MAINTENANCE 237 3 GMV L R90Zd Na K GMV L R112Zd Na K GMV L R125Zd Na K ...