DC INVERTER MULTI VRF INSTALLATION
126
Copper pipe shall not be inserted too much for connection with branch pipe:
6.7 Welding of Copper Pipe
1
)
)
)
)
Braze welding
Materials for braze welding
There are two kinds of braze welding, soft braze welding and hard braze welding. Hard braze
welding is required in this case.
Selection of braze welding
Red red copper
:
brazing filler metal is Bcu93P
(
GB 6418
)
,
and welding flux is not needed.
Flame flux: capable of preventing the surface of copper pipes from oxidation, recommended for
use
Temperature for braze welding
:
820-860
℃
(copper pipe becomes light red)
2
)
)
)
)
Safety acknowledgement before operation
a. Roll calling of construction personnel and confirmation on their health status.
b. Acknowledgement on work suits
(
helmets, clothes, safety bags and safety shoes
)
c. Description of work location and environment
d. Job division shall be made. Job content, method and order shall be indicated. Risk prediction
activities shall be performed.
e. “Construction Schedule” shall be worked out.
f. Head of each group shall be assigned.
g. Risks of occurrence of an accident such as electric shock or fire shall be indicated.
Branch pipe
Copper pipe
Correct connection
Wrong connection
Copper pipe
Correct connection
Wrong connection
Branch pipe
Summary of Contents for GMV(L)-Pd100W/NaB-K
Page 1: ...1 DC INVERTER MULTI VRF Service Manual GREE ELECTRIC APPLIANCES INC OF ZHUHAI ...
Page 4: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 1 PRODUCT ...
Page 40: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 37 CONTROL ...
Page 41: ...DC INVERTER MULTI VRF CONTROL 38 CONTROL 1 OPERATION FLOWCHART ...
Page 43: ...DC INVERTER MULTI VRF CONTROL 40 1 2 Heating Operation ...
Page 70: ...DC INVERTER MULTI VRF CONTROL 67 2 Frame Diagram of System Net 上 WC ...
Page 90: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 87 INSTALLATION ...
Page 115: ...DC INVERTER MULTI VRF INSTALLATION 112 ...
Page 159: ...DC INVERTER MULTI VRF MAINTENANCE 156 MAINTENANCE ...
Page 179: ...DC INVERTER MULTI VRF MAINTENANCE 176 ...
Page 212: ...DC INVERTER MULTI VRF MAINTENANCE 209 2 GMV L R90T Na K GMV L R112T Na K GMV L R125T Na K ...
Page 216: ...DC INVERTER MULTI VRF MAINTENANCE 213 2 GMV L R40P Na K GMV L R45P Na K GMV L R50P Na K ...
Page 224: ...DC INVERTER MULTI VRF MAINTENANCE 221 2 GMV L R36G NaB K GMV L R45G NaB K ...
Page 226: ...DC INVERTER MULTI VRF MAINTENANCE 223 3 GMV L R50G NaB K GMV L R56G NaB K ...
Page 228: ...DC INVERTER MULTI VRF MAINTENANCE 225 4 GMV L R71G Na K GMV L R80G Na K ...
Page 230: ...DC INVERTER MULTI VRF MAINTENANCE 227 5 GMV L R22G NaC K GMV L R28G NaC K ...
Page 232: ...DC INVERTER MULTI VRF MAINTENANCE 229 6 GMV L R36G NaC K GMV L R45G NaC K ...
Page 237: ...DC INVERTER MULTI VRF MAINTENANCE 234 2 GMV L R71Zd Na K ...
Page 240: ...DC INVERTER MULTI VRF MAINTENANCE 237 3 GMV L R90Zd Na K GMV L R112Zd Na K GMV L R125Zd Na K ...