DC INVERTER MULTI VRF INSTALLATION
151
Connection Schematics for Indoor / Outdoor Power Cords and Communication Line
9.4 Dial-up
Gree DC Multi VRF unit is provided with three dial-up, i.e. function dial-up, address dial-up
and capacity dial-up. ou may adjust the function dial-up to set the control, mode and functions of
the unit; adjust the address dial-up to set the matching relation between indoor unit and wired
controller; and adjust the capacity dial-up to set the capacity demands of the indoor unit.
9.4.1 Function Dial-up
CAUTIONS!
The S7 function dial-up is located on the mainboard of indoor unit. It can be
operated only when the client needs to change the default function settings; otherwise the default
position shall be maintained.
Functional description of function dial-up:
DIP swicth 1 (S/R): Setting of memory mode, including the standby mode and restoration mode.
The standby mode refers to that the previous parameters will be kept but the
unit will not run automatically after the power supply is resumed. This setting is
factory defaulted (DIP swicth pulled to “ON” position). For example, if the
parameters of an indoor unit set before power shutdown are High Fan and 24
℃
,
the unit will be under standby state after the power supply is resumed and after
the unit is manually started, the parameters will remain as High Fan and 24
℃
.
The restoration mode refers to that not only the previous parameters will be kept,
but also that the unit can start automatically after the power supply is resumed.
But if the unit is under STOP state before power shutdown, it will be also under
STOP state after the power supply is resumed.
DIP swicth 2 (L/I): Setting of control mode, including wired control and remote control. The wired
control mode refers to that the indoor unit is controlled from wired controller
(wired controller). This setting is factory defaulted (DIP swicth pulled to “ON”
position). When the setting is wired control mode, the function dial-up on S7 for
“setting of memory mode” and “setting of master / slave indoor unit” will be
disabled. These two settings can be done from the wired controller directly. The
remote control mode refers to that the indoor unit is controlled from remote
controller. When the setting is remote control mode, its function dial-up must be
set on S7.
DIP swicth 3 (M/S): The setting of master / slave indoor unit refers to the master / slave setting of
indoor run mode, mainly used to meet the needs of special people on priority
(e.g. leader, patients, etc). The factory default setting is that all indoor units are
master (DIP swicth pulled to “ON” position).
Functional dial switch S7
Dial-up Setting
DIP
swicth
Functional Description:
0 (ON Position)
1
1(S/R)
Setting of memory
mode
Standby (S)
Restore (R)
2(L/I)
Setting of control mode
Wired control
(L)
Remote
control (I)
3(M/S)
Setting of master / slave
indoor unit
Master indoor
unit (M)
Slave indoor
unit (S)
4(I/O)
Setting of ambient
temperature acquisition
point
Return air inlet
(I)
Receiver (O)
5(L/H)
Setting of high / low
static pressure fan
Low static
pressure (L)
High static(H)
Summary of Contents for GMV(L)-Pd100W/NaB-K
Page 1: ...1 DC INVERTER MULTI VRF Service Manual GREE ELECTRIC APPLIANCES INC OF ZHUHAI ...
Page 4: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 1 PRODUCT ...
Page 40: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 37 CONTROL ...
Page 41: ...DC INVERTER MULTI VRF CONTROL 38 CONTROL 1 OPERATION FLOWCHART ...
Page 43: ...DC INVERTER MULTI VRF CONTROL 40 1 2 Heating Operation ...
Page 70: ...DC INVERTER MULTI VRF CONTROL 67 2 Frame Diagram of System Net 上 WC ...
Page 90: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 87 INSTALLATION ...
Page 115: ...DC INVERTER MULTI VRF INSTALLATION 112 ...
Page 159: ...DC INVERTER MULTI VRF MAINTENANCE 156 MAINTENANCE ...
Page 179: ...DC INVERTER MULTI VRF MAINTENANCE 176 ...
Page 212: ...DC INVERTER MULTI VRF MAINTENANCE 209 2 GMV L R90T Na K GMV L R112T Na K GMV L R125T Na K ...
Page 216: ...DC INVERTER MULTI VRF MAINTENANCE 213 2 GMV L R40P Na K GMV L R45P Na K GMV L R50P Na K ...
Page 224: ...DC INVERTER MULTI VRF MAINTENANCE 221 2 GMV L R36G NaB K GMV L R45G NaB K ...
Page 226: ...DC INVERTER MULTI VRF MAINTENANCE 223 3 GMV L R50G NaB K GMV L R56G NaB K ...
Page 228: ...DC INVERTER MULTI VRF MAINTENANCE 225 4 GMV L R71G Na K GMV L R80G Na K ...
Page 230: ...DC INVERTER MULTI VRF MAINTENANCE 227 5 GMV L R22G NaC K GMV L R28G NaC K ...
Page 232: ...DC INVERTER MULTI VRF MAINTENANCE 229 6 GMV L R36G NaC K GMV L R45G NaC K ...
Page 237: ...DC INVERTER MULTI VRF MAINTENANCE 234 2 GMV L R71Zd Na K ...
Page 240: ...DC INVERTER MULTI VRF MAINTENANCE 237 3 GMV L R90Zd Na K GMV L R112Zd Na K GMV L R125Zd Na K ...