DC INVERTER MULTI VRF MAINTENANCE
1.2
Display Code on Digital Tube of Outdoor Mainboard
Error
Display
on
Digital
Tube
Display on
Indoor
Unit
Error
Display
on
Digital
Tube
Display on
Indoor
Unit
DC overvoltage
protection
PH
E5
Input overcurrent protection
PA
E5
Module overheat
protection
P8
E5
Jumper fault
C5
No display
Current test circuit
fault
Pc
E5
Recharging circuit fault
PU
E5
Module temperature
sensor fault
P7
E5
High-pressure protection
E1
E1
Compressor
overcurrent protection
P5
E5
Low-pressure protection
E3
E3
DC undervoltage
protection
PL
E5
Exhaust protection
E4
E4
Compressor startup
failure
Lc
E5
Compressor overload protection
H3
E5
PFC module
protection
Hc
E5
Communication fault (between
indoor / outdoor unit and wired
controller)
E6
E6
Drive resetting and
stop
P0
E5
Outdoor ambient temperature
sensor error
F4
F4
Protection of
compressor against
loss of
synchronization
H7
E5
Indoor coil inlet temperature
sensor error
F5
F5
Compressor
protection against
loss of phase
Ld
E5
Indoor coil middle temperature
sensor error
F6
F6
Inverter drive
communication fault
P6
E5
Outdoor coil outlet temperature
sensor error
F7
F7
IPM module
protection
H5
E5
Exhaust temperature sensor
error
F9
F9
1.3
Display of the number of indoor units
Note: You may press down SW3 key of outdoor unit twice continuously within 2s, so that the system will detect
the number of indoor units, in which case the LED1
~
LED4 will blink in turn, LED5 and LED6 will become dark.
After 12 seconds, the number of indoor units will be displayed.
Lamp display
Number of indoor
units
LED6
LED5
LED4
LED3
LED2
LED1
1
Dark
Dark
Dark
Dark
Dark
Bright
2
Dark
Dark
Dark
Dark
Bright
Dark
3
Dark
Dark
Dark
Dark
Bright
Bright
4
Dark
Dark
Dark
Bright
Dark
Dark
5
Dark
Dark
Dark
Bright
Dark
Bright
6
Dark
Dark
Dark
Bright
Bright
Dark
:
:
:
:
:
:
:
:
:
:
:
:
:
:
62
Bright
Bright
Bright
Bright
Bright
Dark
63
Bright
Bright
Bright
Bright
Bright
Bright
Summary of Contents for GMV(L)-Pd100W/NaB-K
Page 1: ...1 DC INVERTER MULTI VRF Service Manual GREE ELECTRIC APPLIANCES INC OF ZHUHAI ...
Page 4: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 1 PRODUCT ...
Page 40: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 37 CONTROL ...
Page 41: ...DC INVERTER MULTI VRF CONTROL 38 CONTROL 1 OPERATION FLOWCHART ...
Page 43: ...DC INVERTER MULTI VRF CONTROL 40 1 2 Heating Operation ...
Page 70: ...DC INVERTER MULTI VRF CONTROL 67 2 Frame Diagram of System Net 上 WC ...
Page 90: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 87 INSTALLATION ...
Page 115: ...DC INVERTER MULTI VRF INSTALLATION 112 ...
Page 159: ...DC INVERTER MULTI VRF MAINTENANCE 156 MAINTENANCE ...
Page 179: ...DC INVERTER MULTI VRF MAINTENANCE 176 ...
Page 212: ...DC INVERTER MULTI VRF MAINTENANCE 209 2 GMV L R90T Na K GMV L R112T Na K GMV L R125T Na K ...
Page 216: ...DC INVERTER MULTI VRF MAINTENANCE 213 2 GMV L R40P Na K GMV L R45P Na K GMV L R50P Na K ...
Page 224: ...DC INVERTER MULTI VRF MAINTENANCE 221 2 GMV L R36G NaB K GMV L R45G NaB K ...
Page 226: ...DC INVERTER MULTI VRF MAINTENANCE 223 3 GMV L R50G NaB K GMV L R56G NaB K ...
Page 228: ...DC INVERTER MULTI VRF MAINTENANCE 225 4 GMV L R71G Na K GMV L R80G Na K ...
Page 230: ...DC INVERTER MULTI VRF MAINTENANCE 227 5 GMV L R22G NaC K GMV L R28G NaC K ...
Page 232: ...DC INVERTER MULTI VRF MAINTENANCE 229 6 GMV L R36G NaC K GMV L R45G NaC K ...
Page 237: ...DC INVERTER MULTI VRF MAINTENANCE 234 2 GMV L R71Zd Na K ...
Page 240: ...DC INVERTER MULTI VRF MAINTENANCE 237 3 GMV L R90Zd Na K GMV L R112Zd Na K GMV L R125Zd Na K ...