DC INVERTER MULTI VRF CONTROL
51
When the evaporator temperature sensor is in trouble, the evaporator temperature is measured lower than -30
℃
or higer than 100
℃
for one minute continuously,, the evaporator temperature sensor error signal will disappear,
and the indoor unit will operate as the former state.
The measure times should not be accumulatived
◆
Fault Type
Error Code
Indoor ambient temperature sensor error
F0
Indoor tube-inlet sensor error
F1
Indoor tube sensor error
F2
Indoor tube-exit sensor error
F2
1m
1m
1m
1m
<1m
上限值
下限值
t
感温包
温度
感温包故
障状态
故障产生
故障恢复
故障产生
故障恢复
9) Address setting of indoor unit
Indoor unit at the same units must have exclusive address to operate, so you should set the address when
installing the indoor unit.
The address of indoor unit at the same units is not allowed to repeat.
The address of the same indoor unit should conform to the address of remote controller.
The address setting of indoor unit and remote controller should use address DIP switch, which is set on the
mainboard of indoor unit and remote control, and has the sign of “address”.
The address which DIP switch refers to is listed as follows.
Dial-up code table (4 positions DIP switch)
Position
4
Position
3
Position
2
Position
1
Address
Position
4
Position
3
Position
2
Position
1
Address
ON
ON
ON
ON
1
OFF
ON
ON
ON
9
ON
ON
ON
OFF
2
OFF
ON
ON
OFF
10
ON
ON
OFF
ON
3
OFF
ON
OFF
ON
11
ON
ON
OFF
OFF
4
OFF
ON
OFF
OFF
12
ON
OFF
ON
ON
5
OFF
OFF
ON
ON
13
ON
OFF
ON
OFF
6
OFF
OFF
ON
OFF
14
ON
OFF
OFF
ON
7
OFF
OFF
OFF
ON
15
ON
OFF
OFF
OFF
8
OFF
OFF
OFF
OFF
16
Upper limit value
Lower limit value
Sensor fault state
Temperature
of sensor
Error
producing
Error
producing
Error resume
Error resume
Summary of Contents for GMV(L)-Pd100W/NaB-K
Page 1: ...1 DC INVERTER MULTI VRF Service Manual GREE ELECTRIC APPLIANCES INC OF ZHUHAI ...
Page 4: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 1 PRODUCT ...
Page 40: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 37 CONTROL ...
Page 41: ...DC INVERTER MULTI VRF CONTROL 38 CONTROL 1 OPERATION FLOWCHART ...
Page 43: ...DC INVERTER MULTI VRF CONTROL 40 1 2 Heating Operation ...
Page 70: ...DC INVERTER MULTI VRF CONTROL 67 2 Frame Diagram of System Net 上 WC ...
Page 90: ...GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF 87 INSTALLATION ...
Page 115: ...DC INVERTER MULTI VRF INSTALLATION 112 ...
Page 159: ...DC INVERTER MULTI VRF MAINTENANCE 156 MAINTENANCE ...
Page 179: ...DC INVERTER MULTI VRF MAINTENANCE 176 ...
Page 212: ...DC INVERTER MULTI VRF MAINTENANCE 209 2 GMV L R90T Na K GMV L R112T Na K GMV L R125T Na K ...
Page 216: ...DC INVERTER MULTI VRF MAINTENANCE 213 2 GMV L R40P Na K GMV L R45P Na K GMV L R50P Na K ...
Page 224: ...DC INVERTER MULTI VRF MAINTENANCE 221 2 GMV L R36G NaB K GMV L R45G NaB K ...
Page 226: ...DC INVERTER MULTI VRF MAINTENANCE 223 3 GMV L R50G NaB K GMV L R56G NaB K ...
Page 228: ...DC INVERTER MULTI VRF MAINTENANCE 225 4 GMV L R71G Na K GMV L R80G Na K ...
Page 230: ...DC INVERTER MULTI VRF MAINTENANCE 227 5 GMV L R22G NaC K GMV L R28G NaC K ...
Page 232: ...DC INVERTER MULTI VRF MAINTENANCE 229 6 GMV L R36G NaC K GMV L R45G NaC K ...
Page 237: ...DC INVERTER MULTI VRF MAINTENANCE 234 2 GMV L R71Zd Na K ...
Page 240: ...DC INVERTER MULTI VRF MAINTENANCE 237 3 GMV L R90Zd Na K GMV L R112Zd Na K GMV L R125Zd Na K ...