Operation
5
3.6
Stopping the engine in manual mode
Preconditions
Generator is not connected to network.
Engine is running in manual mode.
CAUTION
Stopping the engine when it is running at full load causes extreme stress to the engine.
Risk of overheating, damage to components!
Before stopping the engine, operate it at idle speed until operating temperatures decrease
and stable values are indicated.
Preparation
Item
Task
Engine
After the generator circuit breaker has been opened, allow the engine to cool
down by running it idle for approx. 5 minutes.
Stopping the engine
Item
Task
Switching cabinet, control
panel etc. (depending on
manufacturer)
Press stop button.
Automatic stopping procedure is performed;
Engine is stopped.
After stopping the engine
Item
Task
Cooling pump
Operate for approx. 5 minutes after engine stop.
3.7
Emergency stop
CAUTION
An emergency stop causes extreme stress to the engine.
Risk of overheating, damage to components!
Initiate emergency stop only in emergency situations.
Emergency stop from LOP
Item
Task
EMERGENCY STOP button
Press.
Engine is stopped by switching off power supply to ECU;
Signalization (e.g. by horn, flashing lamp) is released.
M015403/00E 02-09
© MTU
www.generent.ru
Summary of Contents for 12V 4000 G 41
Page 22: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Page 30: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Page 38: ...8 Maintenance Schedule Application Group 3A M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Page 40: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Page 116: ...58 Engine Governor Electronic Control System M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Page 118: ...II Table of Contents M015403 00E 02 09 MTU w w w g e n e r e n t r u...
Page 124: ...w w w g e n e r e n t r u...