54
Engine Mounts
Engine/generator mounting resilient elements
check
1. Wipe rubber surface with dry cloth, do not use
organic detergents.
2. Check resilient elements for crack formation and
deformation by visual inspection.
3. Have cracked elements replaced, contact
Service.
Setting dimension check
1. Measure dimension (a) with Vernier caliper.
2. If dimension (a) is less than 57 mm, resilient elements must be replaced. Contact Service.