Cooling System, General, HT Circuit
HT cooling pump relief bore check
1. Check relief bore for oil and water discharge.
2. Stop engine ( Page 3 5)and disable engine
start.
3. Clean the relief bore with a wire if it is dirty.
Permissible water discharge: up to 10 drops
per hour;
Permissible oil discharge: up to 5 drops
per hour.
4. If discharge exceeds the specified limits: Contact
Service.
M015403/00E 02-09
© MTU