GEK-113308
MIWII Directional Power Protection System
5-5
5 SETTINGS
5.3 ADVANCED SETTINGS
5
5.3ADVANCED SETTINGS
5.3.1 GENERAL ADVANCED
NOTE ABOUT THE TRIP MIN TIME SETTING:
This setting indicates the time during which the tripping contact will remain closed as a minimum in case of fault. If the
fault persists for a longer time than the set value, the tripping contact will remain closed and will be opened immediately
after the fault is cleared, while if the fault is shorter than the set time, the relay will maintain the contact closed for this set
time.
5.3.2 FUNCTION 40 T2 (MIWII1000)
5.3.3 FUNCTION 32 1 T2 (MIWII1000/MIWII2000)
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
GENERAL ADVANCED
ADV. GENERAL
SETTINGS
GENERAL
ADVANCED
Identification
IDENTIFICATION
---
MIWII
Text
NA
Settings Group
Settings Group
Settings Group
1
1-2
NA
Trip Min Time
Trip Min Time
Trip Min Time
200 ms
50-300 ms
1 ms
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 40 T2
40 T2
FUNCTION 40
Enable 40 T2
40 Enable T2
Enable 40
NO
YES/NO
NA
Volt Superv 40 T2
Enable Voltage Supervision T2 Volt Superv 40
YES
YES/NO
NA
Voltage Level 40 T2
Voltage Level T2
Voltage Level 40
0.70
0.70 to 1.00 Vn
0.01
Trip Enable 40 1 T2
Enable Circle 1 Trip T2
Trip Enable 40 1
NO
YES/NO
NA
Diam Circle 40 1 T2
Circle 1 Diameter T2
Diam Circle 40 1
25 Ohm
1 to 300 Ohm
0.1
Offs Circle 40 1 T2
Circle 1 Offset T2
Offs Circle 40 1
2.5 Ohm
1 to 180 Ohm
0.1
Delay Circl 40 1 T2
Circle 1 Trip Delay T2
Delay Circl 40 1
5 s
0.1 to 10 s
0.1
Trip Enable 40 2 T2
Enable Circle 2 Trip T2
Trip Enable 40 2
NO
YES/NO
NA
Diam Circle 40 2 T2
Circle 2 Diameter T2
Diam Circle 40 2
25 Ohm
1 to 300 Ohm
0.1
Offs Circle 40 2 T2
Circle 2 Offset T2
Offs Circle 40 2
2.5 Ohm
1 to 180 Ohm
0.1
Delay Circle40 2 T2
Circle 2 Trip Delay T2
Delay Circl 40 2
5 s
0.2 to 10 s
0.1
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 32 1 T2
32_1 FUNCTION T2
FUNCTION 32 1
Enable 32 1 T2
32_1 Enable T2
Enable 32 1
NO
YES/NO
NA
Trip Enable 32 1 T2
32_1 Trip T2
Trip Enable 32 1
NO
YES/NO
NA
Power 32 1 T2
32_1 Power Type T2
Power 32 1
ACTIVE
ACTIVE / REACTIVE / APPARENT NA
Type 32 1 T2
32_1 Minimum/Maximum T2 Type 32 1
MINIMUM
MINIMUM / MAXIMUM
NA
Direction 32 1 T2
32_1 Forward/Reverse T2
Direction 32 1
FORWARD
FORWARD / REVERSE
0.01
Alarm Level 32 1 T2
32_1 Alarm Level T2
Alarm Level 32 1
0.05
0.01 - 1.5
0.01
Alarm Delay 32 1 T2 32_1 Alarm Delay T2
Alarm Delay 32 1 10 s
0.2 – 120 s
0.1
Trip Level 32 1 T2 32_1 Trip Level T2
Trip Level 32 1 0.05
0.01 – 1.50
0.01
Trip Delay 32 1 T2 32_1 Trip Delay T2
Trip Delay 32 1 10 s
0.2 – 120 s
0.1
Block 32 1 T2
Block 32_1 From Online T2
Block 32 1
1s
0 - 5000
1