GEK-113308
MIWII Directional Power Protection System
6-5
6 I/0 CONFIGURATION
6.2 OUTPUTS AND LEDS CONFIGURATION
6
6.2OUTPUTS AND LEDS CONFIGURATION
6.2.1 DESCRIPTION OF OUTPUTS AND LEDS
MIWII incorporates 6 outputs and 6 LED indicators. 4 of the outputs and LED indicators are user configurable, and can
only be programmed using ENERVISTA MII SETUP software (SETPOINT – RELAY CONFIGURATION). The first two
LEDs are fixed for READY (System ready) and TRIP. The fixed outputs are programmed for ALARM (System alarm) and
TRIP.
The TRIP LED activates when the TRIP contact closes.
The READY LED turns on when all the following conditions are fulfilled:
•
The relay status is READY
•
At least one of the protection functions of the active table is enabled
•
The trip of at least one of the enabled functions is also enabled.
The default configuration for outputs is as follows:
FOR MIWII1000:
FOR MIWII2000:
The default LED configuration is as follows:
FOR MIWII1000:
FOR MIWII2000:
OUTPUT
CONFIGURATION
MEMORY
1
40 Trip
No
2
32_1 Trip
No
3
32_2 Trip
No
4
32_ 3 Trip
No
OUPUTS
CONFIGURATION
MEMORY
1
32_1Trip
No
2
32_2 Trip
No
3
32_3 Trip
No
4
32_4 Trip
No
LED
CONFIGURATION
MEMORY
1
40trip
Yes
2
32_1trip
Yes
3
32_2 trip
Yes
4
32_2 trip
Yes
LED
CONFIGURATION
MEMORY
1
32_1Trip
Yes
2
32_2 Trip
Yes
3
32_3 Trip
Yes
4
32_4 Trip
Yes