8-8
MIWII Directional Power Protection System
GEK-113308
8.5 MENU TREE
8 KEYPAD AND DISPLAY
8
MAIN SETTINGS
FUNCTION 40
Enable 40
Ready-Disable
Volt Superv 40
Ready-Disable
Voltage level 40
0.70-1.00
Trip Enable 40 1
Ready-Disable
Diam Circle 40 1
1.0-300.0
Offs Circle 40 1
1.0-180.0
Delay Circl 40 1
0.1-10.0
Trip Enable 40 2
Ready-Disable
Diam Circle 40 2
1.0-300.0
Offs Circle 40 2
1.0-180.0
Delay Circl 40 2
0.1-10.0
ENTER
ESC
MENU
MIWII
MAIN SETTINGS
ENTER
ESC
Enable 32 1
Enable-Disable
Trip Enable 32 1
READY - [DISABLE]
Power 32 1
ACTIVE - REACTIVE - APPARENT
Type 32 1
[MINIMUM] - MAXIMUN
Direction 32 1
[FORWARD] - REVERSE
Block 32 1
0 - 5000
Alarm Level 32 1
0.01 - 1.50
Alarm Delay 32 1
0.2 - 120.0
Trip Level 32 1
0.01 - 1.50
Trip Delay 32 1
0.2 - 120
MAIN SETTINGS
FUNCTION 32 1
ENTER
ESC
ENTER
ESC
Enable 32 2
Enable-Disable
Trip Enable 32 2
READY - [DISABLE]
Power 32 2
ACTIVE - REACTIVE - APPARENT
Type 32 2
[MINIMUM] - MAXIMUN
Direction 32 2
[FORWARD] - REVERSE
Block 32 2
0 - 5000
Alarm Level 32 2
0.01 - 1.50
Alarm Delay 32 2
0.2 - 120.0
Trip Level 32 2
0.01 - 1.50
Trip Delay 32 2
0.2 - 120
MAIN SETTINGS
FUNCTION 32 2