8-14
MIWII Directional Power Protection System
GEK-113308
8.5 MENU TREE
8 KEYPAD AND DISPLAY
8
ENTER
ESC
MENU
MIWII
MAIN SETTINGS
ENTER
ESC
Enable 32 1
Enable-Disable
Trip Enable 32 1
READY - [DISABLE]
Power 32 1
ACTIVE - REACTIVE - APPARENT
Type 32 1
[MINIMUM] - MAXIMUN
Direction 32 1
[FORWARD] - REVERSE
Block 32 1
0 - 5000
Alarm Level 32 1
0.01 - 1.50
Alarm Delay 32 1
0.2 - 120.0
Trip Level 32 1
0.01 - 1.50
Trip Delay 32 1
0.2 - 120
MAIN SETTINGS
FUNCTION 32 1
ENTER
ESC
Enable 32 2
Enable-Disable
Trip Enable 32 2
READY - [DISABLE]
Power 32 2
ACTIVE - REACTIVE - APPARENT
Type 32 2
[MINIMUM] - MAXIMUN
Direction 32 2
[FORWARD] - REVERSE
Block 32 2
0 - 5000
Alarm Level 32 2
0.01 - 1.50
Alarm Delay 32 2
0.2 - 120.0
Trip Level 32 2
0.01 - 1.50
Trip Delay 32 2
0.2 - 120
MAIN SETTINGS
FUNCTION 32 2