3-6
MIWII Directional Power Protection System
GEK-113308
3.2 WIRING
3 HARDWARE
3
3.2.2 CONTROL POWER
CAUTION: CONTROL POWER SUPPLIED TO THE RELAY MUST MATCH THE RATED VOLTAGE OF THE RELAY. IF
THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY OCCUR.
Table 3–1: CONTROL POWER VOLTAGE RANGE
RANGE
RATED VOLTAGE
OPERATION RANGE
LO
24/48 Vdc
19.2~57.6 Vdc
HI
110/250 Vdc
110/230 Vac
88~300 Vdc
88~264 Vac