9-20
MIWII Directional Power Protection System
GEK-113308
9.14 USER SETTINGS
9 RELAY COMMISSIONING
9
9.14.2 ADVANCED SETTINGS
9.14.2.1 GENERAL ADVANCED
9.14.2.2 FUNCTION 40 (MIWII1000)
9.14.2.3 FUNCTION 32 1
ENERVISTA MII
SETUP
HMI
SETTING
RANGE
STEP
GENERAL ADVANCED
ADV. GENERAL
SETTINGS
GENERAL
ADVANCED
Identification
IDENTIFICATION
---
Text
NA
Settings Group
Settings Group
Settings Group
1-2
NA
Trip Min Time
Trip Min Time
Trip Min Time
50-300 ms
1 ms
ENERVISTA MII
SETUP
HMI
SETTING
RANGE
STEP
FUNCTION 40
40 T2
FUNCTION 40
Enable 40
40 Enable T2
Enable 40
YES/NO
NA
Volt Superv 40
Enable Voltage
Supervision T2
Volt Superv 40
YES/NO
NA
Voltage Level 40
Voltage Level T2
Voltage Level 40
0.70 to 1.00 Vn
0.01
Trip Enable 40 1
Enable Circle 1 Trip T2 Trip Enable 40 1
YES/NO
NA
Diam Circle 40 1
Circle 1 Diameter T2
Diam Circle 40 1
1 to 300 Ohm
0.1
Offs Circle 40 1
Circle 1 Offset T2
Offs Circle 40 1
1 to 180 Ohm
0.1
Delay Circl 40 1
Circle 1 Trip Delay T2
Delay Circl 40 1
0.1 to 10 s
0.1
Trip Enable 40 2
Enable Circle 2 Trip T2 Trip Enable 40 2
YES/NO
NA
Diam Circle 40 2
Circle 2 Diameter T2
Diam Circle 40 2
1 to 300 Ohm
0.1
Offs Circle 40 2
Circle 2 Offset T2
Offs Circle 40 2
1 to 180 Ohm
0.1
Delay Circl 40 2
Circle 2 Trip Delay T2
Delay Circl 40 2
0.2 to 10 s
0.1
ENERVISTA MII SETUP
HMI
SETTING
RANGE
STEP
FUNCTION 32 1
32_1 FUNCTION T2
FUNCTION 32 1
Enable 32 1
32_1 Enable T2
Enable 32 1
YES/NO
NA
Trip Enable 32 1
32_1 Trip T2
Trip Enable 32 1
YES/NO
NA
Power 32 1
32_1 Power Type T2
Power 32 1
ACTIVE / REACTIVE / APPARENT
NA
Type 32 1
32_1 Minimum/Maximum T2
Type 32 1
MINIMUM / MAXIMUM
NA
Direction 32 1
32_1 Forward/Reverse T2
Direction 32 1
FORWARD / REVERSE
0.01
Alarm Level 32 1
32_1 Alarm Level T2
Alarm Level 32 1
0.01 - 1.5
0.01
Alarm Delay 32 1 32_1 Alarm Delay T2
Alarm Delay 32 1
0.2 – 120 s
0.1
Trip Level 32 1 32_1 Trip Level T2
Trip Level 32 1
0.01 – 1.50
0.01
Trip Delay 32 1 32_1 Trip Delay T2
Trip Delay 32 1
0.2 – 120 s
0.1
Block 32 1
Block 32_1 From Online T2
Block 32 1
0 - 5000
1