5-2
MIWII Directional Power Protection System
GEK-113308
5.2 MAIN SETTINGS
5 SETTINGS
5
5.2MAIN SETTINGS
5.2.1 PRODUCT SETUP
5.2.2 FUNCTION 40 (MIWII1000)
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
PRODUCT SETUP
PRODUCT SETUP
PRODUCT SETUP
Relay Status
Relay Operation
Relay Operation
DISABLE
READY / DISABLE
NA
Current CT ratio
CT Ratio
Current CT Ratio
1
1-4000
1
Voltage VT ratio
VT Ratio
Voltage VT ratio
1000
1.00-4000.00
0.01
Nominal Power
Rated MVA
Nominal Power
30.00
0.05-1000.00MVA
0.01
Nominal Voltage
Rated Voltage
Nominal Voltage
11000
100-30000 V
1
Generator Power Factor
Power Factor
Power Fact
0.9
0.05-0.99
0.01
Frequency
Frequency
Frequency
60 Hz
50/60 Hz
NA
ModBus Format
---
ModBus Format
Intel
Intel/Motorola
NA
V App
VT Connection Type
V App
3P WYE
3P WYE/3P DELTA/
1P WYE/1P DELTA
NA
HMI Password
---
HMI Password
1
1-9999
1
Comm Password
---
Comm Password
1
1 – 255
1
Slave Address
---
Slave Address
1
1 – 255
1
Communications Speed
---
Comm Baud Rate
9.6
0.3, 0.6, 1.2, 2.4, 4.8,
9.6, 19.2
NA
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 40
40
FUNCTION 40
Enable 40
40 Enable
Enable 40
NO
YES/NO
NA
Volt Superv 40
Enable Voltage
Supervision
Volt Superv 40
YES
YES/NO
NA
Voltage Level 40
Voltage Level
Voltage Level 40
0.70 Vn
0.70 to 1.00 Vn
0.01
Trip Enable 40 1
Enable Circle 1 Trip
Trip Enable 40 1
NO
YES/NO
NA
Diam Circle 40 1
Circle 1 Diameter
Diam Circle 40 1
25 Ohm
1 to 300 Ohm
0.1
Offs Circle 40 1
Circle 1 Offset
Offs Circle 40 1
2.5 Ohm
1 to 180 Ohm
0.1
Delay Circl 40 1
Circle 1 Trip Delay
Delay Circl 40 1
5 s
0.1 to 10 s
0.1
Trip Enable 40 2
Enable Circle 1 Trip
Trip Enable 40 2
NO
YES/NO
NA
Diam Circle 40 2
Circle 2 Diameter
Diam Circle 40 2
25 Ohm
1 to 300 Ohm
0.1
Offs Circle 40 2
Circle 2 Offset
Offs Circle 40 2
2.5 Ohm
1 to 280 Ohm
0.1
Circle 2 timer
Circle 2 Trip Delay
TIME2 40
5 s
0.2 to 20 s
0.1