GEK-113308
MIWII Directional Power Protection System
B-17
APPENDIX B
B.7 MODBUS MAP - SETTINGS
B
ADRESS
BIT
NAME
DESCRIPTION
LENGTH
FORMAT
013E
7
32_3 Blocked
sBLQ 32 3
2
BIT
013E
8
40 Blocked
sBLQ 40
2
BIT
013E
10
Close Breaker operation
sC INT
2
BIT
013F
9
Protection status
E PROT
2
BIT
013F
10
Output 1
aux1
2
BIT
013F
11
Output 2
aux2
2
BIT
013F
12
Output 3
aux3
2
BIT
013F
13
Output 4
aux4
2
BIT
013F
14
Digital Input 1
ENT1
2
BIT
013F
15
Digital Input 2
ENT2
2
BIT
0140
1
Sett. change disable
ihca
2
BIT
0140
2
Trip operation by input
ORD D
2
BIT
0140
4
Breaker 52B
ED 52B
2
BIT
0140
6
Settings group change
C TAB
2
BIT
0140
7
Oscillo trigg by DI
Gosc
2
BIT
0140
9
Breaker Closed
est INTE
2
BIT
0140
10
Oscillo trigg by comm
STOC
2
BIT
0140
11
40 Voltage inhibit
sI Vol
2
BIT
0140
12
Fuse Failure
sF Fus
2
BIT
0140
13
Settings change
C AJUS
2
BIT
0140
14
EEPROM Failure
SE2P
2
BIT
0140
15
User settings
Adef
2
BIT
0141
0
40 Circle 1 Pickup
A40 1
2
BIT
0141
1
40 Circle 2 Pickup
A40 2
2
BIT
0141
2
32_1 Alarm Pickup
A Alr 32 1
2
BIT
0141
3
32_1 Pickup
A32 1
2
BIT
0141
4
32_2 Alarm Pickup
A Alr 32 2
2
BIT
0141
5
32_2 Pickup
A32 2
2
BIT
0141
6
32_3 Alarm Pickup
A Alr 32 3
2
BIT
0141
7
32_3 Pickup
A32 3
2
BIT
0142
0
40 disabled (by DI)
I E F40
2
BIT
0142
3
32_1 disabled (by DI)
I E 32 1
2
BIT
0142
5
32_2 disabled (by DI)
I E 32 2
2
BIT
0142
7
32_3 disabled (by DI)
I E 32 3
2
BIT
0142
15
Trip disabled (by DI)
D INH
2
BIT
0143
0
40 Circle 1 Trip
D40 1
2
BIT
0143
1
40 Circle 2 Trip
D40 2
2
BIT
0143
2
32_1 Alarm
Alr32 1
2
BIT
0143
3
32_1 Trip
D32 1
2
BIT
0143
4
32_2 Alarm
Alr32 2
2
BIT
0143
5
32_2 Trip
D32 2
2
BIT
0143
6
32_3 Alarm
Alr32 3
2
BIT
0143
7
32_3 Trip
D32 3
2
BIT
0143
15
General trip
DISGEN
2
BIT