5-4
MIWII Directional Power Protection System
GEK-113308
5.2 MAIN SETTINGS
5 SETTINGS
5
5.2.6 FUNCTION 32 4 (MIWII2000)
5.2.7 FUSE FAILURE(MIWII1000)
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUNCTION 32 4
32_4 FUNCTION
FUNCTION 32 4
Enable 32 4
32_4 Enable
Enable 32 4
NO
YES/NO
NA
Trip Enable 32 4
32_4 Trip
Trip Enable 32 4
NO
YES/NO
NA
Power 32 4
32_4 Power Type
Power 32 4
ACTIVE
ACTIVE / REACTIVE / APPARENT NA
Type 32 4
32_4 Minimum/Maximum
Type 32 4
MINIMUM
MINIMUM / MAXIMUM
NA
Direction 32 4
32_4 Forward/Reverse
Direction 32 4
FORWARD
FORWARD / REVERSE
0.01
Alarm Level 32 4
32_4 Alarm Level
Alarm Level 32 4
0.05
0.01 - 1.5
0.01
Alarm Delay 32 4 32_4 Alarm Delay
Alarm Delay 32 4
10 s
0.2 – 120 s
0.1
Trip Level 32 4 32_4 Trip Level
Trip Level 32 4
0.05
0.01 – 1.50
0.01
Trip Delay 32 4 32_4 Trip Delay
Trip Delay 32 4
10 s
0.2 – 120 s
0.1
Block 32 4
Block 32_4 From Online
Block 32 4
1s
0 - 5000
1
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
FUSE FAILURE FUSE FAILURE FUSE FAILURE
Enable Fuse
Fuse Failure Enable
Enable Fuse
NO
YES/NO
NA