B-4
MIWII Directional Power Protection System
GEK-113308
B.3 COMMAND EXECUTION
APPENDIX B
B
Example
:
We send the Group-related command. For instance, to activate Group 2, the selection command will be 15 (0F00H)
Intel Request
:
Intel Reply
:
CONFIRMATION:
Intel Request:
Intel Reply
:
Motorola Request-Motorola Reply
Example:
Request:
To activate Group 2, the selection command will be 0FH; therefore the operation to be performed is a writing of word 0F
00H at the address 00 00H.
The operation confirmation code for Group 2 activation is 16 (10h). In this case, it is necessary to send the relay
password
Intel Request
:
ADDRESS
FUNCTION
BEGINNING
#REGS
#BYTES
DATA0
CRC
01H
10H
0000H
0001H
02H
0F00H
A3A0H
ADDRESS
FUNCTION
BEGINNING
#REGS
CRC
01H
10H
0000H
0001H
01C9H
FIELD
LENGTH
Relay address
1 byte
Function
1 byte (10H)
Beginning address
1 word (0000H) (High byte – low byte)
Number of registers
1 word (0001H) (High byte – low byte)
Number of bytes
1 byte (06H)
Value of the registers
Register1=>Command code (Low byte – High
byte).
Register2=>Relay password (Low byte – High
byte).
Register3=>Constant value
CRC
1 word
FIELD
LENGTH
Relay address
1 byte
Function
1 byte (10H)
Beginning address
1 word (0000H) (High byte – low byte)
Number of registers
1 word (0003H) (High byte – low byte)
CRC
1 word
ADDRESS
FUNCTION
BEGINNING
#REGS
#BYTES
DATA0
DATA1
DATA2
CRC
01H
10H
0000H
0003H
06H
10 00H
01 00H
00 00H
E5ECH